EasyManuals Logo

Emotron AFR 2.0 Series User Manual

Emotron AFR 2.0 Series
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
80 Functional description CG Drives & Automation 01-7318-01r1
* Under normal traffic conditions, i.e. with cyclic bus traffic
above 2 Hz, the baud rate should be detected within
5seconds.
Communication Fault [
264
]
Main menu for communication fault/warning settings. For
further details please see the Fieldbus option manual.
Communication Fault Mode [2641]
Selects action if a communication fault is detected.
Communication Fault Time [2642]
Defines the delay time for the trip/warning.
Ethernet [
265
]
Settings for Ethernet module (Modbus/TCP, Profinet IO).
For further information, see the Fieldbus option manual.
IP Address [2651]
MAC Address [2652]
Subnet Mask [2653]
Gateway [2654]
DHCP [2655]
NOTE:
The automatic baud rate detection will NOT work if
there is no traffic on the network.
Default: Off
Off 0 No communication supervision.
Trip 1
RS232/485 selected:
The AC drive will trip if there is no
communication for time set in parameter
[2642].
Fieldbus selected:
The AC drive will trip if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
Warning 2
RS232/485 selected:
The AC drive will give a warning if there is
no communication for time set in
parameter [2642].
Fieldbus selected:
The AC drive will give a warning if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
NOTE:
Menu [214] and/or [215] must be set to COM to
activate the communication fault function.
Default: 0.5 s
Range: 0.1-15 s
2641 ComFlt Mode
Stp Off
2642 ComFlt Time
Stp 0.5s
NOTE:
The Ethernet module must be re-booted to activate
the below settings. For example by toggling
parameter [261]. Non-initialized settings indicated by
flashing display text.
Default: 0.0.0.0
Default:
An unique number for the Ethernet
module.
Default: 0.0.0.0
Default: 0.0.0.0
Default: Off
Selection: On/Off
2651 IP Address
000.000.000.000
2652 MAC Address
Stp 000000000000
2653 Subnet Mask
0.000.000.000
2654 Gateway
0.000.000.000
2655 DHCP
Stp Off

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron AFR 2.0 Series and is the answer not in the manual?

Emotron AFR 2.0 Series Specifications

General IconGeneral
BrandEmotron
ModelAFR 2.0 Series
CategoryIndustrial Electrical
LanguageEnglish