100 Functional Description Emotron AB 01-3694-01r2
Fig. 87 Steady state test
11.4.9 Pump/Fan Control [390]
The Pump Control functions are in menu [390]. The func-
tion is used to control a number of drives (pumps, fans, etc.)
of which one is always driven by the VSD.
Pump enable [391]
This function will enable the pump control to set all relevant
pump control functions.
Communication information
Number of Drives [392]
Sets the total number of drives which are used, including the
Master VSD. The setting here depends on the parameter
Select Drive [393]. After the number of drives is chosen it is
important to set the relays for the pump control. If the dig-
ital inputs are also used for status feedback, these must be set
for the pump control.
Communication information
time
[711] Process Value
[310] Process Ref
[387]
[712] Speed
[388]
Stop/Sleep
[389]
[389]
[341] Min Speed
[386] PID<Min Spd
Normal PID
Stop steady
Start steady
Steady state
Normal PID
test
state test
state test
Default: Off
Off 0 Pump control is switched off.
On 1
Pump control is on:
- Pump control parameters [392] to [39G]
appear and are activated according to
default settings.
- View functions [39H] to [39M] are added
in the menu structure.
Modbus Instance no/DeviceNet no: 43161
Profibus slot/index 169/65
Fieldbus format UInt
Modbus format UInt
A
391 Pump enable
Stp Off
Default: 1
1-3 Number of drives if I/O Board is not used.
1-6
Number of drives if 'Alternating MASTER' is
used, see Select Drive [393]. (I/O Board is
used.)
1-7
Number of drives if 'Fixed MASTER' is used,
see Select Drive [393].
(I/O Board is used.)
NOTE: Used relays must be defined as Slave Pump or
Master Pump. Used digital inputs must be defined as
Pump Feedback.
Modbus Instance no/DeviceNet no: 43162
Profibus slot/index 169/66
Fieldbus format UInt
Modbus format UInt
A
392 No of Drives
Stp 1