142 Functional Description Emotron AB 01-3694-01r2
11.9 View Trip Log [800]
Main menu with parameters for viewing all the logged trip
data. In total the VSD saves the last 10 trips in the trip
memory. The trip memory refreshes on the FIFO principle
(First In, First Out). Every trip in the memory is logged on
the time of the Run Time [731] counter. At every trip, the
actual values of several parameter are stored and available for
troubleshooting.
11.9.1 Trip Message log [810]
Display the cause of the trip and what time that it occurred.
When a trip occurs the status menus are copied to the trip
message log. There are nine trip message logs [810]–[890].
When the tenth trip occurs the oldest trip will disappear.
Communication information
Trip message [811]-[81N]
The information from the status menus are copied to the
trip message log when a trip occurs.
Communication information
Example:
Fig. 116 shows the third trip memory menu [830]: Torque
trip occurred after 1396 hours and 13 minutes in Run time.
Fig. 116 Trip 3
Unit: h: m (hours: minutes)
Range: 0h: 0m–65355h: 59m
Modbus Instance no/DeviceNet no: 31101
Profibus slot/index 121/245
Fieldbus format UInt
Modbus format UInt
Trip menu Copied from Description
811 711 Process Value
812 712 Speed
813 712 Torque
814 714 Shaft Power
815 715 Electrical Power
816 716 Current
817 717 Output voltage
818 718 Frequency
819 719 DC Link voltage
81A 71A Heatsink Temperature
81B 71B PT100_1, 2, 3
81C 721 VSD Status
8x0 Trip message
Stp h:mm:ss
810 Ext Trip
Stp 132:12:14
81D 723 Digital input status
81E 724 Digital output status
81F 725 Analogue input status 1-2
81G 726 Analogue input status 3-4
81H 727 Analog output status 1-2
81I 728 I/O status option board 1
81J 729 I/O status option board 2
81K 72A I/O status option board 3
81L 731 Run Time
81M 732 Mains Time
81N 733 Energy
Modbus Instance no/DeviceNet no: 31102 - 31134
Profibus slot/index
121/246 - 254,
122/0 - 23
Fieldbus format UInt
Modbus format UInt
Trip menu Copied from Description
830 Over temp
Stp 1396h:13m