Emotron AB 01-4429-01r2 Functional Description 109
Communication information
Min Pre Alarm Response delay [4182]
Sets the delay time between the first occurrence of min pre
alarm condition and after when the alarm is given.
Communication information
Min Alarm [419]
Min Alarm Margin [4191]
With load type Basic, [415], used the Min Alarm Margin
sets the band under the Normal Load, [41B], menu that
does not generate an alarm. With load type Load Curve,
[415], used the Min Alarm Margin sets the band under the
Load Curve, [41C], that does not generate an alarm. The
Max Alarm Margin is a percentage of nominal motor
torque.
Communication information
Min Alarm Response delay [4192]
Sets the delay time between the first occurrence of min
alarm condition and after when the alarm is given.
Communication information
Autoset Alarm [41A]
The Autoset Alarm function can measure the nominal load
that is used as reference for the alarm levels. If the selected
Load Type [415] is Basic it copies the load the motor is run-
ning with to the menu Normal Load [41B]. The motor
must run on the speed that generates the load that needs to
be recorded. If the selected Load Type [415] is Load Curve it
performs a test-run and populates the Load Curve [41C]
with the found load values.
Communication information
Modbus Instance no/DeviceNet no: 43328
Profibus slot/index 169/232
Fieldbus format Long, 1=1%
Modbus format EInt
Default: 0.1 s
Range: 0-90 s
Modbus Instance no/DeviceNet no: 43332
Profibus slot/index 169/236
Fieldbus format Long, 1=0.1 s
Modbus format EInt
Default: 15%
Range: 0-400%
Modbus Instance no/DeviceNet no: 43329
Profibus slot/index 169/233
Fieldbus format Long, 1=1%
Modbus format EInt
Default: 0.1 s
Range: 0-90 s
Modbus Instance no/DeviceNet no: 43333
Profibus slot/index 169/237
Fieldbus format Long, 1=0.1 s
Modbus format EInt
WARNING: When autoset does a test run the
motor and application/machine will ramp up
to maximum speed.
NOTE: The motor must be running for the Autoset Alarm
function to succeed. A not running motor generates a
“Failed!” message.
Default: No
No 0
Yes 1
Modbus Instance no/DeviceNet no: 43334
Profibus slot/index 169/238
Fieldbus format UInt
Modbus format UInt