Commissioning Proline Promass 83 PROFIBUS DP/PA
102 Endress+Hauser
Example 2:
a0002664
Fig. 46: In this configuration example, modules that are not needed are replaced by the EMPTY_MODULE. The
Promass 83 GSD file is used.
With this configuration, the Analog Input function block 1(slot 1), the totalizer value TOTAL (slot
7) and the cyclic control of device functions CONTROL_BLOCK (slot 11) are activated. The mass
flow (factory setting) is read out cyclically by the measuring device by means of the Analog Input
function block. The totalizer is configured “without configuration”. In other words, in this example
it only returns the totalizer value for the mass flow by means of the TOTAL module and cannot be
controlled by the automation device.
Slot sequence Module
Byte length
input data
Byte length
output data
Description
1AI5–Analog Input function block 1
Output variable → Mass flow (factory setting)
Data structure → Page 90
2EMPTY_MODULE––Empty
3EMPTY_MODULE––Empty
4EMPTY_MODULE––Empty
5EMPTY_MODULE––Empty
6EMPTY_MODULE––Empty
7TOTAL5–
Totalizer function block 1
Output variable for TOTAL → Mass flow (factory setting)
8EMPTY_MODULE––Empty
9EMPTY_MODULE––Empty
10 EMPTY_MODULE – – Empty
11 CONTROL_BLOCK – 1 Control of device functions