Technical data Proline Promass 83 PROFIBUS DP/PA
148 Endress+Hauser
Measuring ranges for liquids (Promass H, I):
Measuring ranges for liquids (Promass A):
Measuring ranges for liquids (Promass E):
Measuring ranges for gases (except Promass H)
The full scale values depend on the density of the gas. Use the formula below to calculate the full
scale values:
g
max(G)
= g
max(F)
ρ
(G)
/ x [kg/m
3
]
g
max(G)
= Max. full scale value for gas [kg/h]
g
max(F)
= Max. full scale value for liquid [kg/h]
ρ
(G)
= Gas density in [kg/m
3
] at operating conditions
x = 160 (Promass F DN 8...100, M, I); x = 250 (Promass F DN 150...250); x = 225 (Promass E);
x = 32 (Promass A)
Here, g
max(G)
can never be greater than g
max(F)
Calculation example for gas:
Sensor type: Promass F, DN 50
Gas: air with a density of 60.3 kg/m
3
(at 20 °C and 50 bar)
Measuring range: 70000 kg/h
x = 160 (for Promass F DN 50)
Max. possible full scale value:
g
max(G)
= g
max(F)
ρ
(G)
/ x [kg/m
3
] = 70000 kg/h 60.3 kg/m
3
÷ 160 kg/m
3
= 26400 kg/h
DN Range for full scale values (liquids) g
min(F)
...g
max(F)
8 0...2000 kg/h
15 0...6500 kg/h
15 * 0...18000 kg/h
25 0...18000 kg/h
25 * 0...45000 kg/h
40 0...45000 kg/h
40 * 0...70000 kg/h
50 0...70000 kg/h
* DN 15, 25, 40 “FB” = Full bore versions of Promass I
DN Range for full scale values (liquids) g
min(F)
...g
max(F)
1 0...20 kg/h
2 0...100 kg/h
4 0...450 kg/h
DN Range for full scale values (liquids) g
min(F)
...g
max(F)
8 0...2000 kg/h
15 0...6500 kg/h
25 0...18000 kg/h
40 0...45000 kg/h
50 0...70000 kg/h