Proline Promass 83 PROFIBUS DP/PA Commissioning
Endress+Hauser 85
5. Configuration of totalizers 1-3:
Promass 83 has 3 totalizers. The following example applies to totalizer 1.
• In the “CHANNEL” parameter, select the measured variable (e.g. mass flow) to be
transmitted to the PROFIBUS master as the totalizer value 1:
BASIC FUNCTION (G) → PROFIBUS PA (GCA) → TOTALIZER (613)...
... → SELECT TOTALIZER (6130) → Select: TOTALIZER 1
... → CHANNEL (6133) → Select: MASS FLOW
or enter the ID: 277
Possible settings: see following table.
• Enter the desired totalizer units:
BASIC FUNCTION (G) → PROFIBUS DP/PA (GBA) → TOTALIZER (613)
→ UNIT TOTALIZER (6134)
• Configure totalizer status, e.g. totalise:
BASIC FUNCTION (G) → PROFIBUS DP/PA (GBA) → TOTALIZER (613)
→ SET TOTALIZER (6135) → Select: TOTALISE
• Set the totalizer mode, e.g. for balancing:
BASIC FUNCTION (G) → PROFIBUS DP/PA (GBA) → TOTALIZER (613)
→ TOTALIZER MODE (6137) → Select: BALANCE
The following settings are possible:
6. Select the operating mode (GSD file) which should be used for cyclic communication with the
PROFIBUS master.
BASIC FUNCTION (G) → PROFIBUS PA (GCA) → OPERATION (614)
→ SELECTION GSD (6140) → Select:
– MANUFACT. SPEC. (factory setting): Promass 83 measuring device is operated in the
manufacturer-specific mode.
– MANUFACT V2.0: Promass 83 is used as the replacement for the previous Promass 63
model (compatibility mode).
– GSD PROFILE: Promass 83 is operated in the Profile mode.
!
Note!
For PROFIBUS network configuration, make sure that the right device master file (GSD file) of
the measuring device is used for the selected operating mode:
!
Note!
Further information on the device master file → Page 86
7. Configuration of cyclic data communication in the PROFIBUS master:
A detailed description of the system integration can be found on → Page 86.
Measured variable ID for “CHANNEL” parameter
Mass flow (factory setting totalizers 1...3) 277
Volume flow 273
Corrected volume flow 398
Operating mode Device master file (GSD-file)
MANUFACT. SPEC. “eh3x152A.GSD” or “eh3_152A.GSD” (depends on the PROFIBUS master used)
MANUFACT V2.0 “eh3x1506.GSD” or “eh3_1506.GSD” (depends on the PROFIBUS master used)