Commissioning Proline Promass F 300 EtherNet/IP
116
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Pulse width In the Operating mode
parameter, the Pulse option is
selected, and one of the
following options is selected in
the Assign pulse output
parameter (→  115):
Mass flow
Volume flow
Corrected volume flow
Target mass flow
*
Carrier mass flow
*
Define time width of the
output pulse.
0.05 to 2 000 ms 100 ms
Failure mode In the Operating mode
parameter, the Pulse option is
selected, and one of the
following options is selected in
the Assign pulse output
parameter (→  115):
Mass flow
Volume flow
Corrected volume flow
Target mass flow
*
Carrier mass flow
*
Define output behavior in
alarm condition.
Actual value
No pulses
No pulses
Invert output signal Invert the output signal. No
Yes
No
* Visibility depends on order options or device settings
Configuring the frequency output
Navigation
"Setup" menu → Pulse/frequency/switch output
Pulse/frequency/switch output
1 to n
Operating mode
→  117
Terminal number
→  117
Signal mode
→  117
Assign frequency output
→  118
Minimum frequency value
→  119
Maximum frequency value
→  119
Measuring value at minimum
frequency
→  120