PROline Prosonic Flow 93 PROFIBUS-DP/-PA 6 Commissioning
Endress+Hauser 87
Procedure (determining data for sensor installation)
You can use the following tables to select and configure, in the correct order, the func-
tions required to install the sensor:
“Clamp On” sensor installationPage 87
“Insertion” sensor installationPage 89
“Liquid sound velocity” measurement (only for Clamp On)Page 90
“Pipe sound velocity” measurement (only for Clamp On)Page 91
“Wall thickness” measurement (only for Clamp On)Page 92
!
Note!
You must enter a valid release code before device parameters can be changed or
activated. The code (factory setting = 93) is entered by means of the corresponding
matrix cell. This is V2H0 for Commuwin II.
Commuwin II: You can use the VAH5 matrix cell to select various partial matrixes
required for configuration.
“Clamp On” sensor installation
Procedure
Selection - Input - display
Local display (Quick Setup)
FieldTool
Commuwin II
BASIC FUNCTION
SENSOR DATA CH1/CH2
SENSOR PARAM.
BASIC FUNCTION
SENSOR DATA CH1/CH2
SENSOR PARAM.
Manufacturer-specific Transducer
Block “PROSONIC 93 PBUS”:
SENSOR DATA (VAH5)
SENSOR PARAM. CH1/CH2
Type of measurement MEASUREMENT (6880) MEASUREMENT MEASUREMENT
CH1 (V3H0) / CH2 (V6H0)
Sensor type SENSOR TYPE (6881) SENSOR TYPE SENSOR TYPE CH1 (V3H1)
SENSOR TYPE CH2 (V6H1)
Sensor configuration SENSOR CONFIGURATION
(6882)
SENSOR CONFIGURATION SENSOR CONFIG. CH1 (V3H2)
SENSOR CONFIG. CH2 (V6H2)
BASIC FUNCTION
PROCESS PARAM. CH1/CH2
PIPE DATA
BASIC FUNCTION
PROCESS PARAM. CH1/CH2
PIPE DATA
Manufacturer-specific Transducer
Block “PROSONIC 93 PBUS”:
DE. MATRIX CH1/2 (VAH5)
PIPE DATA CH1/CH2
Standard pipe selection PIPE STANDARD (6520) PIPE STANDARD PIPE STANDARD CH1/CH2
(V4H0)
Nominal diameter pipe NOMINAL DIAMETER (6521) NOMINAL DIAMETER NOMINAL DIAMETER CH1/CH2
(V4H1)
Pipe material PIPE MATERIAL (6522) PIPE MATERIAL PIPE MATERIAL CH1/CH2 (V4H2)
Pipe sound velocity SOUND VELOCITY PIPE (6524) SOUND VELOCITY PIPE SOUND VELOC. PIPE CH1/CH2
(V4H4)
Pipe circumference CIRCUMFERENCE (6525) CIRCUMFERENCE CIRCUMFERENCE CH1/CH2
(V4H5)
Pipe diameter PIPE DIAMETER (6526) PIPE DIAMETER PIPE DIAMETER CH1/CH2 (V4H6)
Wall thickness WALL THICKNESS (6527) WALL THICKNESS WALL THICKNESS CH1/CH2
(V4H7)