E-IOC-107 Info YES Firmware upgrade successfully performed
on the indicated module.
Message can be deleted by ACK.
E-IOC-108 Error Firmware upgrade successfully performed
on the indicated module.
Please contact service.
E-RIV-101 Warning The selected dosing unit is not compatible
with the set controller type.
Adjust the dosing unit settings.
E-RIV-102 Configured alarm was triggered.
E-RIV-103 Error A required hardware module is not avail-
able.
Retrofit the appropriate hardware and per-
form a hardware scan, or select a suitable
application.
E-RIV-105 Maintenance interval no further specified.
E-RIV-106 Error General runtime error. Check the actuator feedback of the servo-
motor.
Possible causes:
Missing or incorrect actuator feedback.
Setting wheel unlocked
Electronics error
Check the connections.
Lock the adjusting wheel.
E-RIV-107 Error Servomotor calibration error Check the actuator feedback of the servo-
motor.
E-RIV-109 Info Self-calibration of the servomotor is per-
formed.
Wait until the process is completed.
E-RIV-117 Error Hardware or electronic error in the Indi-
cated module.
Please contact service.
E-RIV-118 Info Communication error in the indicated
module.
Please contact service.
E-RIV-119 Error Input signal outside of measurable range. Check input signal and wiring.