746 C - 844 C 41 532150 - Rev.A
Translation of the original instructions
ENGLISH
4 Addressing Bus 2Easy sensitive edges
Key: 0=OFF , 1=ON
1 1 0 1 CL EDGE
0 1 1 0 OP EDGE
ON
1 2 3 4
BUS 2EASY CONTROL DEVICES
1. Configure the DIP switches on the device to assign
1 o 2 commands ( see table).
i
Stop NC also generates a stop when the device is discon-
nected. A command (e.g.: OPEN A_1) must be used on
only one of the connected devices.
No two devices should have the same address.
If there is more than one device with the same address,
it generates a conflict error on the board and prevents
the automation from working. Detection devices do not
generate conflicts with control devices and vice versa.
2. Register the BUS 2easydevices (§ specific section).
3. Check the Bus 2Easy devices (§ specific section)
and make sure that the automation operates
according to the type of control devices installed.
5 Addressing Bus 2Easy control devices
Key: 0=OFF , 1=ON
DIP switch 5, in the ON position enables the device for 2 commands.
ON
1 2 3 4 5
ON
1 2 3 4 5
0 0 0 0 0 Open A_1 0 0 0 0 1 Open A_1 Open B_1
0 0 0 1 0 Open A_2 0 0 0 1 1 Open A_1 Open B_2
0 0 1 0 0 Open A_3 0 0 1 0 1 Open A_1 Stop
0 0 1 1 0 Open A_4 0 0 1 1 1 Open A_1 Close
0 1 0 0 0 Open A_5 0 1 0 0 1 Open A_2 Open B_1
0 1 0 1 0 Stop 0 1 0 1 1 Open A_2 Open B_2
0 1 1 0 0 *Stop NC_1 0 1 1 0 1 Open A_2 Stop
0 1 1 1 0 *Stop NC_2 0 1 1 1 1 Open A_2 Close
1 0 0 0 0 Close 1 0 0 0 1 Open A_3 Open B_3
1 0 0 1 0 Open B_1 1 0 0 1 1 Open A_3 Open B_4
1 0 1 0 0 Open B_2 1 0 1 0 1 Open A_3 Stop NC_1
1 0 1 1 0 Open B_3 1 0 1 1 1 Open A_3 Close
1 1 0 0 0 Open B_4 1 1 0 0 1 Open A_4 Open B_3
1 1 0 1 0 Open B_5 1 1 0 1 1 Open A_4 Open B_4
1 1 1 0 0 / 1 1 1 0 1 Open A_4 *Stop NC_2
1 1 1 1 0 / 1 1 1 1 1 Open A_4 Close
E.g.: In order to have OPEN A on different connected devices, set
OPEN A_1 on the first and OPEN A_2 or OPEN A_3 on the second...
*Stop NC also generates a stop when the device is disconnected. If
you do not require this function, use one “Stop".