It will not be possible to enable/disable separately
the two output channels.
+
The separated programming of the Sounder and
Beacon of the devices (named previously), it will be
possible also by Control Panel User Interface in the
Devices programming pages.
n
Multiple Input-Output Module - Parameters
Programming (FC410MIO/FC410QIO)
Click on an entered Multiple Input/Output Module
FC410MIO (3 Inputs and 4 Outputs Module) or
FC410QIO (4 Inputs and 4 Outputs Module), see the
customized Manuals, the relevant programming win
-
dow will be shown.
The options descriptions are as per the Input and Out
-
put Modules paragraphs. In the field “Label” a
description of Input/Output Module will be inserted.
For Trigger Points see same section on "Output module
parameters programming".
OPTIONS section:
Ø
Oppo interface: ActUnit/KeySafe, allows you to
manage the procedure for the automatic opening of
the doors of the factory / Office / Shop, Warehouse,
in case of fire. This avoids the breakage of these
structures. The outputs of this module can control
these actions.
Ø
LED blinking: click on to enable/disable signaling LE.
The FC410TSM Door Control Module (one Input/one
output) designed to close a fire door in case of alarm or
fault. The FC410TSM monitors:
- the external Power supply;
- Loop voltage Test, if the relevant option are enabled.
+
In an eventual connection on the right side (2 wires
connection), the module enables the yellow (isola-
tor) LED blinking (Not correct installation)
n Manual Call Point parameters programming
Click on a Manual Call Point (FC420CP, FC421CP) the
relevant programming will be shown as per the following
description. GENERAL section: as for the detectors;
OPTIONS section:
Ø
assigned zones: each Manual Call Point can be as
-
sociated with 1 of the available software zones (32
for FC501).
Ø
Led blinking: if this option is enabled, the Manual
Call Point LED will blink every Loop scanning.
Zones programming
The Zones option from the panel tree menu will al
-
low you to access the software-zone parameters
(see Figure 25). The software zones parameters
will be applied automatically to all the devices asso
-
ciated with the zone concerned.
GENERAL section (FIRST section);
Ø
Enabled:atick[
3] indicates that the zone is ena
-
bled.
Ø
Label: this is for the editable device-label (up to
20 characters). The system will use the label as
the zone identifier.
OPTIONS section: a number of parameters can be
programmed in this section.
Walk test:
Ø
Active: if this option is enabled, the zones in alarm
status will activate the programmed Outputs with
Walk test event, while the control panel will not gene
-
rate an alarm. Select if the event is fired by:
Any device means Modules + CP + Detectors,
CallPoints means CPs only,
Detectors means Modules + Detectors (No CPs).
Prealarm:
Ø
Prealarm: if this option is enabled, the control panel
will activate the ALARM delay.
Ø
Double Knock: if this option is enabled and the zone
is in Prealarm status, when an other devices (other
address) associated to this zone are activated, the
zone will immediately generate an Alarm status.
+
if "Use zone settings" option is not checked for a de
-
vice, it means that you can individually decide, for
that device, if it has to process Warning and/or Prea
-
larm. Once you have decided that the device proces
-
ses prealarm, its activation will cause Prelarm of the
panel (with panel prealarm time) and, because it be
-
longs to a zone, that zone will go into the prealarm
status. If another point belonging to the zone goes
into Prealarm, the Double Knock option becomes
active if enabled in Zone programming page.
Ø
Prealarm Duration: an input device programmed
with Prealarm time will generate ALARM status
when the prealarm time elapses. (see parameters
programming detector).
Select the Prealarm time.
The prealarm time can be set from 0 seconds to 300
seconds in 1-second steps. Other:
Ø Drift Compensation: see the same option in “Para-
meters detectors Programming”;
Ø Detector Warning: if this option is enabled the con-
trol panel will activate a WARNING signal.
N.B. To activate the Warning option for a Module,
tick the corresponding box on the Module program
-
ming screen.
Ø
Smoke delay: for each zone, you can program the dela
-
yed activation of the smoke detectors. The SMOKE
DELAY (60s/30min) parameter, when set, applies to all
smoke detectors assigned to the selected zone the alarm
verification algorithm as described in the EN54-2, (see
page 51).
PC PROGRAMMING 35
Figure 26 Outputs programming window.