FC460PC Addressable Optical Smoke &
Heat Detector & CO
Detector of high performance, of smoke, temperature
and CO. The use of the three elements of the sensor, in
synergy, allows to determine with accuracy the presence
of all types of fires and at the same time having an excep
-
tional immunity to false alarms.
The functionalities of the FC460PC detector are:
self-monitoring, self-testing, status indicator, remote
LED and threshold compensation. The detector
FC460PC is compatible with the existing bases.
FC410LI - Line Isolator Module
The FC410LI Line Isolator Module is designed to be
used on the FC addressable controller loop circuits. It
monitors the line condition and when detecting a short
circuit will isolate the affected section whilst allowing the
rest of the addressing circuit to function normally.
The purpose of the FC410LI Line Isolator Module is to en
-
sure that, on a looped addressable system, no short circu
-
it fault can disable more detection devices then would be
lost on a conventional non-addressable fire circuit.
FC410MIM - Mini Input Module
The FC410MIM Mini Input module is designed to moni
-
tor fire contacts, such as extinguishing system control,
ventilation control, fire door control etc.The module pro-
vides one identifiable detection spur which is capable of
monitoring multiple normally open contacts or a single
normally closed contact. The FC410MIM may be moun-
ted in any electrical enclosure with sufficient depth to
accommodate FC410MIM and the contacts monitored
by the IN+ and IN- terminals, ie, no field wiring. The re-
mote LED (if required, not supplied) must be located
within the same electrical enclosure.
FC410MIO - Small Addressable Multi I/0
Module
The FC410MIO Multi I/O Module has three class B inputs
and two outputs from latching relays. The class B inputs
can monitor fire contacts such as extinguishing system
control, ventilation control, fire door control etc. The two
relays outputs are dry form C that provide volt-free relay
changeover contacts. A maximum of two HVR800 High
Voltage Relay Modules can be individually driven and
controlled by an FC410MIO if all HVR800s are powered
by 24V dc or 24V ac. In this application, the HVR800s are
controlled by the two latching relays on the FC410MIO. A
maximum of four HVR800 High Voltage Relay Modules
can be individually driven and controlled by an FC410MIO
if all HVR800s are powered by 120V ac or 240V ac. In this
application, the HVR800s are controlled by the four con
-
trol outputs (O1+/O1- to O4+/O4-) on the FC410MIO.
FC410SIO - Single Input/Output Module
The FC410SIO Single Input/Output Module is designed
to provide a monitored open collector input and a volt
free relay changeover output.
FC410SIO can switch up to2A@24Vdc.
FC420CP - Addressable Break Glass
Callpoint (indoor)
FC420CP Addressable Break Glass Callpoint is desi
-
gned to monitor and signal the condition of a switch
contact that is operated by activating the break glass
element. The type of alarm generated by the callpoint is
configured in FireClass Console.The FC420CP call po
-
int meets the requirements of EN54 Pt.11. The
FC420CP is fitted to a standard surface mount plastic
backbox, standard single gang metal plaster box (35
mm for flush mounting) or standard single gang metal
plaster box (25 mm) with backbox.
FC421CP - Addressable Break Glass
Callpoint (outdoor)
FC421CP Weatherproof Addressable Break Glass Cal
-
lpoint is designed to monitor and signal the condition of
a switch contact that is operated by activating the break
glass element. The type of alarm generated by the cal
-
lpoint is configured in FireClass Console. The
FC421CP callpoint meets the requirements of EN54
Pt.11. The FC421CP is fitted into a standard weather
-
proof break glass callpoint housing.
FC430SAB/SAM - Sounder Base Address
Modules
The Sounder Base Address Modules (FC430SAM
/FC430SAB) are designed to control a loop powered
sounder base for use with the FCsystem, one variant
(FC430SAB) has an integral beacon. They may also be
used to drive a relay base. The units are used to supply
the address decoding in place of a detector, thus provi-
ding a loop powered sounder when used in conjunction
with an FC430SB. The modules are colour matched to
the sounder bases. The FC430SAM/FC430SAB is loc-
ked into the base using the locking device integral to the
sounder base.
FC430SB - Loop Low Power Sounder Base
The FC430SB Loop Low Power Sounder Base provides
an additional sounder function on the FC addressable
loop circuit. The FC430SB Loop Low Sounder Base re
-
quires an associated detector in order to operate, as it
uses the address of the detector that is fitted to it. Remo
-
val of the detector or loss of power to the loop will cause
the sounder to cease operating. A maximum of 45 Soun
-
der Bases at full volume may be connected to the loop.
4B-I - Isolator Base
The FC460/FC400 Series Detectors, as supplied, use a
common 4B-I Isolator Base assembly.
The base may be fixed directly to:
Ø
British (fixing centres 50mm) or European (fixing
centres 70mm) conduit box;
Ø
FC450EMB Euro Mounting Box;
Ø
Directly to the ceiling.
64 Addressable Fire Panel FC501