FC501 control panel via the addressable loop.
Tone, volume and flash rates are set in FireClass Console.
The sounder has four volume settings ‘High’ (90dB ±3),
‘Mid High’ (80 ±3dB), ‘Mid Low’ (70 ±3dB)or ‘Low’ (60dB
±3). The beacon has two flash rates ‘Slow Flash’
(1/2Hz) or ‘Fast Flash’ (1Hz).The FC430LP Series have
a built-in line isolator.
FC430LPBSB Loop Powered Addressable
Sounder/Beacon Base (EN54-23)
The FC430LPBS Series of Loop Powered Addressable
Sounder/Sounder- Beacons are designed to be driven
from an FC501 control panel via the addressable loop.
Tone, volume and flash rates are set in FireClass Console.
The sounder has four volume settings ‘High’ (90dB ±3),
‘Mid High’ (80 ±3dB), ‘Mid Low’ (70 ±3dB)or ‘Low’ (60dB
±3). The beacon has two flash rates ‘Slow Flash’
(1/2Hz) or ‘Fast Flash’ (1Hz).
The FC430LPBS Series have a built-in line isolator.
The table below, cross connect the managed devices in
the current version and the new EN54-23.
+
It is possible to substitute old devices with corre
-
spondent new ones (EN54-23), keeping the same
program data. When the old device is physically re
-
moved from the loop, the control panel will signal
the "No answer" fault. When the new device with
the same address is connected to the loop, the
control panel will restore the "No answer" fault and
automatically update its internal database with the
new device type.
It is not possible to substitute new devices
(EN54-23) with old ones (they are not EN54-23 ap-
proved).
FC410SNM Sounder Notification Module
The FC410SNM Sounder Notification Module is desi
-
gned to provide an output, in response to a command
signalled from a controller, to activate a number of pola
-
rised and suppressed sounders. The sounders are po
-
wered from an independent power supply and the
module is capable of passing up to a maximum of 2A
(eg, 24V dc 50mA company sounders or a mixture of
different current rated sounders not exceeding a maxi
-
mum current of 2A).
+
The possibility of the configuration of extinction, al
-
though present in the FC410SNM module, is not
available for FC501 control panel.
FC410TSM – door control module
The FC410TSM Door Control Module is designed to
close a fire door in case of alarm or fault. The door is
normally kept open by electromagnets. The door con
-
trol module disconnects the electromagnets from power
supply in order to allow the door to close. The
FC410TSM has a relay changeover output and a moni
-
tored input. The FC410TSM contains an integrated line
isolator and self-monitoring circuits (monitoring of com
-
munication with a panel, loop power monitoring), which
enables the fire door to be closed when communication
with a panel is lost for longer than 45s (±5s) or the loop
power drops below Umin=19V for more than 15s (± 5s).
In addition, the FC410TSM monitors the external 24V
supply.
FC410DDM – Universal fire and gas
detector module
The FC410DDM provides the ability to connect and in
-
terface 2 zones of 20 V DC 2-wire conventional fire de
-
tectors, or two 4-20 mA signalling sensors, to the
FireClass fire alarm controller. The FC410DDM moni
-
tors the status of the detectors and the wiring to the de
-
tectors and signals detector and wiring status back to
the controller. The conventional detector circuits can be
configured in one way: To monitor 1 or 2 Class B spur
circuits The 4-20 mA signalling sensors may be one of
two types:
Ø
Current sinking
Ø
Current sourcing.
FC410QIO Quad input output module
The module provides four monitored digital inputs and
four potential free relay changeover outputs.
The outputs are monitored with parallel contacts of the
relays. The outputs can be connected to an Auxiliary Vol-
tage source and its voltage can be monitored. Additio-
nally, all the outputs can be connected to the HVR800,
for switching high power galvanic isolated loads. For
more details refer to the HVR800 documentation.The
module has an integral loop isolator. If this activates a
yellow LED illuminates. The activation remains in place
until the short is removed. The digital input monitoring
and isolator functions are both configurable.
Maximum relay current: 2A.
Maximum relay voltage: 30V.
FC410QRM Quad relay module
The module provides four voltage free relay changeo
-
ver outputs. The outputs are monitored, with parallel
contacts of the relays. The outputs can be connected to
an Auxiliary Voltage source and its voltage can be mo
-
nitored. Additionally, all the outputs are configurable to
the HVR (High Voltage Relay) mode, which allows you
to connect up to four HVR800 modules for switching; for
example 240V loads galvanically isolated.
The module has an integral loop isolator. If this activa
-
tes a yellow LED illuminates. The activation remains in
place until the short is removed.
Maximum relay current: 2A.
Maximum relay voltage: 30V.
FC410QMO Quad Monitored Output
Module
The module comprises of four relays with selectable wi
-
ring supervision.
The output wiring is monitored for any short or open cir
-
cuit. Spur and Loop configurations are supported.
ACCESSORY 67