MP69-Duct Probe Unit
The MP69 Duct Probe units are designed to be installed
in air conditioning supply and exhaust ducts for the pur
-
pose of monitoring the airflow for smoke and combu
-
stion products.
The Duct Probe Units are designed to accept and will
operate satisfactorily with the 600 and FC400 Series
detectors. The Duct Probe units are factory fitted with
the FireClass Universal Base 5B.
FIRERAY 50/100-Optical Beam Smoke
Detector
The Detector comprises a Transmitter and Receiver
contained within one enclosure.
The Transmitter emits an infrared light beam that is re
-
flected via a prism mounted directly opposite and with a
clear line of sight. The reflected infrared light is detected
by the Receiver and analysed.
The Detector has a maximum lateral detection defined
by the local National Standard. As a guide a common
lateral distance of 7.5m will be used in this guide. Use
the latest beam detector standards EN54 part 12,
VdS2095 or BS5839 part 1 for further guidance.
The optimal beam distance from the ceiling will be bet
-
ween 500mm and 600mm, again the Local National
Standard will give guidance.
range: Fireray100 = 50-100 meter
Fireray50 = 5-50 meter
Coverage area: Fireray100 = up to 1500 sqm.
Fireray50 = up to 750 sqm.
FC410LPSY and FC410LPAV loop
powered sounders and sounder-beacons
The FC410LP Series of Loop Powered Addressable
Sounder/ Sounder-Beacons are designed to be driven
from an FireClass control panel via the addressable
loop. The FC410LP Series of sounders/sounder bea
-
cons consist:
FC410LPSYR:Sounder (indoor use) - red housing
FC410LPSYW:Sounder (indoor use) - white housing
FC410LPSY:Sounder IP65 (outdoor use) - red housing
FC410LPAVR:Sounder-Beacon (indoor use) - red hou
-
sing
FC410LPAVW:Sounder-Beacon (indoor use) - white
housing
FC410LPAV:Sounder-Beacon IP65 (outdoor use) - red
housing
The sounder has two volume settings ‘High’ (103 dB ±3)
or ‘Low’ (90 dB ±3).
The beacon has two flash rates ‘Slow Flash’ (1/2 Hz) or
‘Fast Flash’ (1 Hz).
The FC410LP devices are synchronised, but not
synchronous with other FireClass sounders
(FC410SNM) and beacons (FC430SAB).
The first flash of the beacon is synchronised with the
start of the tone.
The FC410LP devices have a built in two port isolator.
FC410LPBS-R/W loop powered sounders
and sounder-beacons (EN54-23)
The FC410LPBS Series of Loop Powered Addressable
Sounder/ Sounder-Beacons are designed to be driven
from a FC501 control panel via the addressable loop.
The FC410LPBS Series of sounders/sounder beacons
consist:
FC410LPBS-R: Sounder (indoor use) - red housing
FC410LPBS-W: Sounder (indoor use) - white housing
FC410LPAV: Sounder-Beacon IP65 (outdoor use) - red
housing
The sounder has two volume settings ‘High’ (103 dB ±3)
or ‘Low’ (90 dB ±3).
The beacon has two flash rates ‘Slow Flash’ (1/2 Hz) or
‘Fast Flash’ (1 Hz).
The FC410LPBS devices are synchronised, but not
synchronous with other FireClass sounders and beacons
of the FC400 serie.
The first flash of the beacon is synchronised with the start
of the tone.
The FC410LPBS devices have a built in two port isolator.
FC430LPSB and FC430LPASB Loop
Powered Addressable Sounder/Beacon
Base
The FC430LP Series of Loop Powered Addressable Soun
-
der/Sounder- Beacons are designed to be driven from an
66 Addressable Fire Panel FC501
FireClass Product
code (Current Dev.)
FireClass Device
name (Current Dev.)
Description
FireClass
Product code
(EN54-23 Dev.)
FireClass
Device name
(EN54-23 Dev.)
516.800.758 FC430LPASB
Loop Powered Beacon
Sounder Base
516.800.973 FC430LPBSB
516.800.763 FC410LPAVR
Loop Powered
Beacon/Sounder (indoor use)
red
516.800.970
FC410LPBS-R
516.800.764 FC410LPAVW
Loop Powered
Beacon/Sounder (indoor use)
white
516.800.971 FC410LPBS-W
516.800.766 FC410LPAV
Loop Powered
Beacon/Sounder IP65
(outdoor use)
516.800.972
FC410LPBS