Programming Page
From the MAIN page, use the 1 Key to select the Pro
-
gramming phase. Insert the password (installer code)
and then the page, in Figure 39, is shown: in this phase:
Alphanumeric keypad Use the Alphanumeric keypad
to select the different programming functions:
0= L3 PWD; start the page to insert the password of L3
level (Installer code) (see Insert-Modify password
page);
1= Auto: start the auto-learning of the loop devices and
the RS485 network devices (Repeater only);
2= FC Dev: start the selection and programming page
of the loop devices;
3= SW Zones: start the programming page of the sof
-
tware zones;
4=Outputs: start the programming page of the Outputs;
5= Network: start the programming page of the RS485
network, FC500MFI modules;
6=Map Device: activates the "On Demand device map
-
ping" feature;
7=USB: start the programming page for the manage
-
ment of the USB memory stick;
8=System: start the programming page of the system
parameters;
9=Default: forces a default setting restore procedure;
Cursor keys
No function is related to UP, Down,
Right and Left key.
ESC Key
Use ESC key to cancel the operation and to
step back to MAIN page.
ENTER Key
No function is related to ENTER key.
0 KEY - insert Modify password
Inside the PROGRAM page, press the 0 key for the di
-
splay (see figure 40): in this phase: Installer Code at
Default is 00000; every digit will be masked by * symbol.
+
See the Installer and User features in relation to the
password on page 8
Alphanumeric keypad Use the Alphanumeric keypad
to insert the password of 5 digit. The first digit must be 0
for the installer 1 (Main Installer) and 9 for the next one.
+
The panel will verify the correct entry of the identifi
-
cation digit, in the case of error a denial tone is ge
-
nerated
Cursor keys
No function is related to UP,Down,Right
and Left key.
ESC Key Short press: aborts the enter password proce
-
dure and moves back the User Interface to calling page;
Long press: clears all the entered digits.
ENTER key Accepts the password and starts the pa
-
ssword verification process.
+
If a wrong or not allowed password is entered,
the Figure 40b will be displayed for 5s..
In order to avoid the entering of a duplicated password
(two different users/installers with the same password)
the users and installers are driven to use a specific digit
as first digit of their password, in this way the most signi
-
ficant digit acts as user/installer identifier.
The first digit for USER #1 is: 1
The first digit for USER #2 is: 2
The first digit for USER #3 is: 3
The first digit for USER #4 is: 4
The first digit for USER #5 is: 5
The first digit for USER #6 is: 6
The first digit for USER #7 is: 7
The first digit for USER #8 is: 8
The first digit for INSTALLER #1 is: 0
The first digit for INSTALLER #2 is: 9.
1 KEY- Auto Enrolling (Autolearning)
The Auto option from the PROGRAMMING menu will
allow you to enrol the loop devices and the RS485 net-
work devices automatically (repeater FC500REP only)
The Auto option consists of three main phases: 1-Auto
enrolling, 2- Auto addressing, 3- Devices mapping (see
notes on page 57, 58).
+
Auto enrolling (Autolearning) can be done during
the installation phase and after changes of the loop
and network configurations.
46 Addressable Fire Panel FC501
FC501 Panel lev.3 :PROGRAM
1=Auto 2=Device 3=SW Zone 4=Output
5=Network 6=Map. Dev. 7=USB 8=System
9=Default 0=L3 PWD
Figure 39 Program Page window
FC501 Panel lev.3 : PROGRAM
INSTALLER 1
Modify any Installer Password
[_____]
Field to insert password
a)
Access Level
If blinking
control panel
working properly
Control panel status
Control Panel name
FC501 Panel lev.3 : PROGRAM
INSTALLER
Wrong Password
b)
Figure 40 Insert/Modify Password window