INSTALLATION
!
Installation of this system must be carried out
strictly in accordance with the instructions in
this section, and in compliance with the local
safety regulations in force.
Prior to commencing installation of the control panel,
ensure that adequate precautions are taken to prevent
damage to the sensitive electronic components on the
display board and the control board due to electrostatic
discharge. You should discharge any static electricity
you may have accumulated by touching a convenient
earthed object such as an unpainted copper radiator
pipe. You should repeat the process at regular intervals
during the installation process.
To install the fire panel work through the following steps:
Ø
choose suitable mounting locations for the Control pa
-
nel, detectors, fire warning and fire control devices.
+
The panel must be located in a clean, dry position,
which is not subject to shock or vibration and at le-
ast 2 metres away from pager systems or any other
radio transmitting equipment.
Ø Lay the cables between the Control panel and the
system peripherals.
+
Fire alarm cables must be separated from all other
wiring (not related to the fire alarm system).
Ø
If necessary, install any accessory modules.
Ø
Carry out the necessary connections, leaving the po
-
wer-supply connection until last.
Ø
Program the Control panel in accordance with the in
-
structions in the “PROGRAMMING” section.
Ø
Test the entire system (Control panel, detectors, fire
warning and fire control devices).
+
FC500IP module (Accessory Modules) should be
installed before mounting the Control panel as de
-
scribed in the paragraph: FC500IP module Instal
-
lation.
!
Ensure that the Control panel power supply
(Mains and Batteries) has been disconnected
before installing any accessory Modules.
Installing the Control panel
Work carefully through the following steps (see the Fi
-
gures 1 and 2).
1. Remove the screws (4) and open the Control panel.
2. Drill the anchor screw holes 7 and 14.
+
Check for water pipes and electrical wiring before
drilling.
+
When using 12Ah batteries use mounting holes 19
to provide additional support.
+
Use the Tubular spirit level (23) for leveling the Pa
-
nel backplate
!
Check for water pipes and electrical wiring be-
fore drilling.
3. If necessary, remove the surface conduit wire knoc-
kouts 2.
+
The cable conduit union with the cabinet must be
secured by HB Flame Class (or higher) lock nuts.
4. Pull the channeled undertrack cables through the
cable entry 11 and 20 (for the power supply cable)
then, using the anchor screws locations, secure the
backplate to the wall.
+
Use anchors 12, (for the power supply cable) and
21 to secure the cables through the cable ties.
n
Control panel closure
To close the panel:
1. Attach the cover to the hooks (6) and then rotate the
cover down.
2. Use the screws (4) to secure the cover on the
backplate.
Installing FC500REP Repeater
Repeaters can be wall mounted, or flush mounted to an
ave
®
BL08 outlet box (or similar).
Work carefully through the following steps.