16 Addressable Fire Panel FC501
P. Description
42 Protection Fuse: F 6.3A 250V
43 Main Power LED
44 Hole for switching Power supply fixing
45 Thermal probe connector
46 Fine trimmer for the Switching-power-supply
output Voltage
47 Auxiliary power-supply terminals (27.6 V)
48 Mains power terminals (230 V 50/60 Hz)
49 Switching-power-supply fixing screw
50 Cable for connecting Main Module
51 Protection Fuse: F 2A 250V
52 Switching-power-supply closure plastic rivet
53 Switching-power-supply anchor
* NOTE (1)
Before connecting the Fire control panel to PC for the
PC programming phase, remove the jumper 34 (“ )of
main board. After the programming phase is finished,
replace the jumper otherwise the Earth fault (Leakage
to Earth) will not be detected.
AC/N
FG
+V
GND
B+
L
B–
GND
+V
AC/L
F 2A/25ØV
F6.3A/25ØV
B+
L
B–
GND
+V
F6.3A/25ØV
F 2A/25ØV
42 43
44
45
46
47
48
49
50
52
53
51
BA
60T24
The BAQ60T24 is suitable when the use of an
add-on units (FC500IP) is required or the loop
current exceeds 250mA or the Auxiliary 24V
output current required is greater than 250mA.
42 43
44
45
46
47
48
49
50
52
53
51
BAQ35T24
The BAQ35T24 is suitable for basic systems
where no add-on (FC500IP) is used, the loop
current is 250mA or less & the Auxiliary 24Vdc
output current is 250mA or less.
Figure 4 BAQ35T24 and BAQ60T24 Switching-power-supply