Description of the FC500REP Repeater
Signalling
n
FC500REP Repeater Control keys
+
Test, Silence Buzzer and Evacuate Control keys
ONLY can be activated without password (access
level L1), all the others Control keys can be activa
-
ted with password (access level L2 and L3) (see
table n.3).
n
FC500REP Repeater LED description
In the table n. 5, the FC500REP LED descriptions are
shown.
10 Addressable Fire Panel FC501
LEDs DESCRIPTION
FIRE Glowing indicates Alarm status. In the event of an Alarm, the Control panel will activate the
unbypassed alarm outputs.
More Alarms Glowing indicates more Alarm status.
Pre-alarms Blinking indicates Pre-alarm status.
Communicator
(Red)
Glowing indicates that transmission was successful.
Blinking indicates that transmission is in progress.
The control panel display will show the connection type: PSTN, GSM, or LAN network.
FAULT Glowing indicates the presence of a Fault: the following LEDs or the screen on the display indicate
the type of the Fault. Slow blinking indicates a fault event in memory (Reset turns OFF ).
Logic Unit Glowing indicates a blocked Control panel. IMPORTANT: Maintenance required.
NOTE When the Control panel is switched on for the first time, this LED will blink until a Reset has
been performed.
Lost Device Glowing indicates that a Loop device has disappeared (missing address).
Communicator
(Amber)
Glowing indicates the Dialer has been disabled; Slow blinking indicates that the dialer has broken
down
(SC)Nac Fire
Output
Glowing indicates that SC FIRE Output is bypassable (disabled), Slow blinking indicates the pre
-
sence of a Fault on SC FIRE Output.
Earth Glowing indicates a Voltage leakage to Earth.
IMPORTANT: Check wiring insulation
Low Battery Glowing indicates Batteries empty or faulty. If this condition persists, the batteries will be unable to
function as intended in the event of blackout, IMPORTANT: New batteries required.
NO Battery Glowing indicates Batteries empty or disconnected ; check if the connections are correct.
MAINS
(amber)
Glowing indicates Mains failure (230 V) or Switching Power supply fault. During this condition,
the Control panel will be powered by the batteries.
Day mode Glowing indicates that the Control panel is operating in Day Mode
OFF indicates that the Control panel is operating in Night Mode
Disabled Glowing indicates the Disabled status of any bypassable entity.
Silence Glowing indicates that Silenceable outputs have been forced to standby by means of SILENCE key;
in Day Mode the SILENCE will remain until the SILENCE key will not been pressed again,
while in Night Mode after the Silence Time expires automatically the SILENCE will end.
Test Glowing indicates Test conditions on at least one zone.
MAINS
(Green)
OFF indicates Mains failure (230 V).
IMPORTANT: Power must be restored before the batteries empty.
Table 3 Description of the status LEDs