EN54-2 certification applies ONLY when OC1 and
OC2 outputs are not C and /or J and/or G (EN 54-1)
type. Therefore this output MUST NOT UTILIZED
to manage Fire Alarm device and/or Fire/Fault
transmission devices and/or Automatic Fire alarm
system.
24R [M]
Reset able auxiliary power supply to devices
that operate at 24 V (0.5A max) (powered by the
standby batteries):
ØPositive (27.6 V) on terminal [24R];
ØNegative on terminal [M].
+
This power supply is disconnected during the reset
of the Control Panel (about 2 s) so it is suitable for
devices that are restored when power supply is di-
sconnected.
24A [M]
Auxiliary Power supply to devices that ope
-
rate at 24 V (0.5A max) always present and guaranteed
by the batteries:
Ø Positive (27.6 V) on terminal [24A];
Ø
Negative on terminal [M].
n
RS485
24V|–|+|M
Terminals for FC500REP repeater (maxi
-
mum 4) and FC500MFI module (maximum 4) (0.5A
max).
Ø
Serial bus terminals [+] and [-];
Ø
27.6 V power voltage terminals [M] and [24V].
+
The maximum cable run allowed is 1000m.
n Battery
+BAT- Terminals to connect the batteries inside the
FC501 control panel.
The System Wiring
!
High Voltage leads (230 V) must be bunched se-
parately from Low Voltage leads (24 V). All le
-
ads must be bunched in such a way as to avoid
contact with other wiring and components.
n
Connecting Addressable Devices
The control panel has 3 loops for addressable analogue
devices.
22 Addressable Fire Panel FC501
+
-
A+ A+A+
(a) (b)
3k93k9 3k93k9
1N4002 1N40021N4002
SC 1
+
-
SC 1
Figure 9 Wiring diagram of the connection of a single device (a) and several devices (b) to Bell outputs (device acti
-
vated by positive (27.6 V) on terminal [A+]).
24A NC
NO
+
–
C
+N
–L –A
+–+–
SC1
1N4002 1N4002 2K7
Self-powered siren
CALL-R24
Flasher Bell
FC501
Figure 10 Wiring diagram: NON-silenceable and Silenceable Output connections