EasyManua.ls Logo

FireClass FC501 - Audio Station

FireClass FC501
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ces that are activated with the positive (24V) and must
be supervised.
During standby status: negative pull-down to 0 V on [+]
terminal; positive pull-up to 27.6 V on the [–] terminal.
When control panel is in alarm status: positive pull-up to
27.6 V on the [+] terminal; negative pull-down to 0 V on
the [–] terminal.
SC1 can be Silenced (forced to standby) by the menu
command DISABLE.
+
This output is not programmable, it is activated every
time the control panel goes into ALARM status.
SC2 (Sounder Circuit Supervised/Silencea
-
ble/Bypassable (Disabled), Programmable Bell out
-
put, for the Panel Alarm signalling or Panel Pre-Alarm
or Panel Warning or Panel Fault or 1,2,3 or 4 Softwa
-
re zones(OR) Alarm, or 1,2,3 or 4 Software zo
-
nes(OR) Pre-alarm, or 1,2,3 or 4 Software zones(OR)
Warning or 1,2,3 or 4 Software zones(OR) Fault or
1,2 or 3 Points(OR) Alarm or 1,2 or 3 Points(OR)
Pre-Alarm or 1,2 or 3 Points(OR) Warning or 1,2 or 3
Points(OR) Fault.
During standby status: negative pull-down to 0 V on [+]
terminal; positive pull-up to 27.6 V on the [–] terminal.
When a programmed event occurs: positive pull-up to
27.6 V on the [+] terminal; negative pull-down to 0 V on
the [–] terminal.
+
The SC1 and SC2 outputs can be forced to
standby by resetting the control panel.
The SC Outputs will hold standby status for the pro
-
grammed Silence Time. If Alarm conditions are present
when the programmed Silence Time expires for the
SC1 or another programmed event for the SC2, they
will re-activate.
+
SC1, SC2 accept devices that operate within
SELV limits ONLY.
+
The SC2 output, if programmed as SC1, will be of
type C.
+
If the 2-wire connection loop is used, the EN54-2
certification applies ONLY when the total number
of devices (detectors, manual callpoints etc.) does
not exceed 32.
n
Audio station
MIC|SPK|BLK|RED Terminals for future use.
20 Addressable Fire Panel FC501
L-L-
L-
L-
L-
L-
L+L+
L+
L+
L+
L+
L-L-
L+L+
+L2-
A
C
BB
BB
A
FC501
+L2-+L1-+L1-
LEFT RIGHT LEFT RIGHT
+L3-+L3-
LEFT RIGHT
Figure 6 1) Wiring diagram of a 2-wire connection, a) Isolators; b) Compatible analogue devices (Fire detector, Input
modules, Output modules, Manual callpoints); c) T connection
.

Table of Contents

Related product manuals