FireClass FC501 - Auto Addressing Procedure

FireClass FC501
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENTER Key
The ENTER key accept the device selec
-
tion and activate the loop device programming
.
+
Attention: when the Enrolling is done, the devices
programming data (except their assigned names)
will restore to the factory defaults; therefore a pre
-
vious configuration will be lost (Selection 1).
Auto addressing procedure
For auto-addressing is intended a sequence of operation
that allows to the installer to make all the devices acces
-
sible by the panel without executing any previous confi
-
guration action on the devices , during their installation
phase (device acquire phase).This involves for the in
-
staller, no longer necessary the use of the FC490ST, the
programming Tool of the Loop devices, and conse
-
quently is no longer needed the procedure for the ma
-
nual assignment of the devices addresses. Furthermore
the auto-addressing procedure have to be able to allow
to the installer to know or set the geographical position of
the devices in the site (device mapping phase).
The Auto addressing procedure is part of the loop devi
-
ces enroll process in the FC501 panel. The loop devi
-
ces enroll process is initiated by the installer:
- press the 1 key to enter in PROGRAMMING mode.
Enter the Installer PIN (00000) at default, each digit will
be masked by
* (star).
- Select option 1: AUTO (see notes on page 57, 58).
After all the devices are initialized in Loop: the panel will
prompt to choose the type of automatic zones assig
-
nment :
1 = according to the Loop
2 = based on the addresses of the devices
3 = do not assign.
Made the choice, the panel get to the results phase:
Ø
press the ENTER key to activate the
AUTOADDRESSING phase;
Ø
or press ESC to the FAULT page (not addressable
devices)
By default, any addressable device has the address 255;
the fire panel examines the serial number of each device
and assigns each an address from 1 to 128.
If the control panel finds a device with a different address
than default (255) it leaves the address set at that device.
+
The control panel is ready to work, at this time,
(with the default basic programming)
48 Addressable Fire Panel FC501
DEVICE MAPPING RUNNING 0=stop
Evt time type add counter 017
016 10:15:33 PH L1:---
017 10:17:19 PH L1:---
AUTO ADDRESSING END
Found: 018 detectors, 004 modules
ENT to DEVICE MAPPING, ESC to exit
DEVICE MAPPING STOPPED 1=run
Evt time type add done:000/022
001>10:15:33 PH L1:---< enter the add.
002 10:17:19 PH L1:---
DEVICE MAPPING STOPPED 1=run
Evt time type add done:017/022
--- unique RIM L1:---< enter the add.
--- unique LPAV L2:---
DEVICE MAPPING STOPPED 1=run
Evt time type add done:001/022
001>10:15:33 PH L1:089< ENT to config.
002 10:17:19 PH L1:---
DEVICE MAPPING STOPPED 1=run
Evt time type add done:020/022
--->*active*LPSB L3:---<enter the add.
--- --:--:--LPSB L3:---
DEVICE MAPPING STOPPED 1=run
Evt time type add done:018/022
--->unique RIM L1:015< ENT to config.
--- unique LPAV L2:---
DEVICE MAPPING STOPPED 1=run
Evt time type add done:021/022
--->--:--:--LPSB L3:005<ENT to config.
--- --:--:--LPSB L3:---
EXIT
MAIN PAGE
DEVICE MAPPING PHASE
(charge of the Installer)
BASIC DEVICE
CONFIGURATION PHASE
N
otes:
AUTO ADDRESSING RUNNING
PLEASE WAIT
ESC to exit
Master panel Lev.3: Program
Detector: 50 Modules: 44
Iloop=073 mA (400ma MAX)
Not addressed dev.> ENT to AUTO-ADDRESS
PANEL IS READY TO WORK
AT THIS TIME
(with the default basic programming)
MS: Det 089 lev.3 :PROGRAM
WORKING MODE Master panel
[First flo ]
^
MS: Det 089 lev.3 :PROGRAM
DEVICE NAME Master panel
MS: Det 089 lev.3 :PROGRAM
ASSIGNED ZONE Master panel
[First flo ]
^
MS: Det 089 lev.3 :PROGRAM
DEVICE NAME Master panel
[First flo ]
^
MS: Det 015 lev.3 :PROGRAM
TRIGGER ZONE EVENT Master panel
[First flo ]
^
MS: Det 089 lev.3 :PROGRAM
DEVICE NAME Master panel
MS: Det 015 lev.3 :PROGRAM
TRIGGER ZONE#1 Master panel
[First flo ]
^
MS: Det 089 lev.3 :PROGRAM
DEVICE NAME Master panel
MS: Det 015 lev.3 :PROGRAM
TRIGGER ZONE#1 Master panel
[First flo ]
^
MS: Det 015 lev.3 :PROGRAM
DEVICE NAME Master panel
[First flo ]
^
MS: Det 005 lev.3 :PROGRAM
TRIGGER ZONE EVENT Master panel
[First flo ]
^
MS: Det 089 lev.3 :PROGRAM
DEVICE NAME Master panel
MS: Det 005 lev.3 :PROGRAM
TRIGGER ZONE#1 Master panel
[First flo ]
^
MS: Det 089 lev.3 :PROGRAM
DEVICE NAME Master panel
MS: Det 005 lev.3 :PROGRAM
TRIGGER ZONE#1 Master panel
[First flo ]
^
MS: Det 005 lev.3 :PROGRAM
DEVICE NAME Master panel
[First flo ]
^
BY WALKING
(Panel +installer)
ESC
ESC
ESC
0
]
EXIT
MAIN PAGE
DEVICE ACQUIRING
(charge of the Panel)
BY DEVICE
“Unique”, in the time field, indicates that it is the only device of it's type on the loop.
For example if only one FC410DDM module is used in the system, it is tagged as “Unique”
so it is not necessary to activate it , the installer knows where it is.
“Active”, in the time field, indicates that the relevant device is active, it is applicable ONLY
to the output device type like sounders, beacons, SNM modules, etc.,
When the installer, scanning the list of previously auto-addressed devices, reaches an
output-only device type, this device becomes active (a sounder starts to sound, a beacon
starts to flash, an output module illuminates its LED) until a new device is selected or the
permanent address is entered. In this way it will be possible to locate where the device is.
EXIT
FAULT PAGE
(not addressable devices)
ESC
EXIT
FAULT PAGE
(not addressable devices)
Figure 42 Autoaddressing scheme