ON, the relevant event will be shown on the display.
Prealarm duration: an input device programmed with
Prealarm time will generate ALARM status when the
prealarm time elapses.
Prealarm status is signalled by: an audible signal emit
-
ted by the control panel;
Ø
blinking on the PREALARM LED (this LED is on the
Repeater FC500REP only);
Ø
the message on the display;
Ø
activation of outputs with programmed Prealarms.
Silence duration: when the control panel is in Night
Mode the Silence delay is the maximum silence time of
the Outputs.
Reset: program the Reset time ( min Time: 2 sec; max
Time: 15 sec.).
The THRESHOLDS section is reserved for the DDM
Gas Detector;
Ø
SET: allows you to choose between 4 levels of thre
-
shold. In the section SET VALUES, the relevant de
-
fined values are connected to the chosen threshold.
After the DDM Gas device is selected in the loop, set
the same level threshold.
Communicators Programming
The Communicators page is for programming the para
-
meters of the PSTN interface, of the FC500IP module
and of Panel events, as described below.
PSTN interface The PSTN interface section is activa-
ted, after the PSTN Telecom interface has been ena-
bled on the General Options page (Figure 27).
In the OPTIONS section:
Ø Call attempts Set the maximum number of at-
tempts that the PSTN interface makes for each Te-
lephone Number: set from 1 to 9, the default setting
is 3 attempts.
Ø Iterations Set the number of times the PSTN inter-
face repeats the Voice Message: set from 1 to 9, the
default setting is 3;
Ø
Tone Check If enabled , the PSTN interface con
-
trols whether it could obtain a Dialling Tone,ifitcould
obtain it move to the next step, otherwise it will consider
the phone call failed, hang up and try again;
Ø
Call All Telemonitoring If the Call all Telemonito
-
ring numbers option is enabled, the PSTN Interface
calls all the numbers which have been programmed
for the event which has occurred, up to the time
when all telephone calls succeed or, at the most,
for the number of Call Attempts which has been
programmed. If the Call All Telemonitoring
numbers option is disabled, the PSTN Interface
will interrupt the call as soon as it succeeds.
Ø
If the Call All Voice Messages numbers option is
enabled (default setting), the PSTN Interface will
call all programmed numbers for the event which
has occurred, until all phone calls fully succeed ac
-
cording to the number of Call Attempts which have
been programmed.
If the Call All Voice Messages numbers option
is disabled, the PSTN Interface will interrupt the
calls as soon as one is successful.
In the section PLAY MESSAGE AFTER, sets the con
-
dition for the playing back of the Voice Message.
Ø
Dialing - the Message is played back as soon as the
Telephone number is dialled.
Ø
Voice - the message is played back when the PSTN
Interface detects a voice answer.
Ø
Delay - the Message is played back when the pro
-
grammed Delay elapses after that the Telephone
number has been dialled: the Delay could be set
from 0 up to 99 seconds, with 1 second steps; the de
-
fault setting is 0 seconds.
In the section PERIODIC REPORT: sets the parameters
corresponding to the Period Test, as described below:
Ø
Date and Time First Test Set the date and time for
the first Periodic Test.
Ø
Period Set the interval between two Periodic Tests:
the interval can be set from 1 up to 25 hours, in steps
of one hour; the default setting is 24 hours.
+
The Periodic Test event IS NOT recorded in the
Events Log.
The section ADDRESS BOOK is used to program
the telephone numbers that can be used to send:
-Voice Messages (Dialler function) or
-Telemonitoring data,
when the events, recognized by the panel, will occur.
In the case of Telemonitoring, select:
the type of protocol (SIA, ADEMCO Contact ID) and:
Customer Code.
Phone numbers are:
-only for alarms;
-only Faults,
-and numbers of general use.
In the section VOICE MESSAGES parameters re-
lated to voice messages are programmed , as descri-
bed below.
(1-7) MESSAGES These messages (from 1 up to 7)
are NOT editable.
(8-32) MESSAGES In this section, a description of 20
characters max, can be assigned to messages from n.
8n.32.
Allows to listen a present message.
Allows to stop the message playback.
Allows to delete the selected message.
38 Addressable Fire Panel FC501