SPECIFICATIONS
This specifications is for installers with knowledge of the
control panels, and fire control panels in general.
Technical features
Some of the technical features, regarding the terminals
on the Main, are described in the following paragraph.
The following table shows the technical features of the
Repeater FC500REP.
REPEATER FC500REP
Operating voltage 27.6Vdc
Maximum current 80mA
Temperature range -5 to +40°
Storage Temperature -40 to +80 °C
Operating Humidity
Up to 95%
non-condensing
Dimensions (W*H*D) 390x215x50 mm
Weight 2.05 Kg
Description of the terminals
The terminals of the Main board and Switching power
supply, are described briefly in the Table 11: the
standby (normal) status is the first, followed by the
alarm status. Moreover, the Voltage present during the
different operating conditions is indicated for each ter-
minal, as well as the maximum current (in amps) that
can circulate.
+
Notes (1) and (2) are valid for the table 10.
Notes (3) and (4) are valid for the table:
" MAX WITHDRAWABLE CURRENT"
1) For the power supply of the external devices. (see
table 11).
2) Connect a 3900 ohm resistor between the [+] and [-]
terminals of the SC1, SC2 Outputs, if not used (see ta
-
ble 11).
3) The sum of the currents of SC1 and SC2 must not
exceed 500 mA.
4) The sum of the currents of 24A and 24R must not ex
-
ceed 500 mA.
SPECIFICATIONS 69
Control Panel FC501-L/FC501-H/FC501-HK
Main voltage 230 V~ 50/60 Hz -15/+10%
Aux. Outputs
Nominal Voltage
27.6V
Aux. Outputs Min.
and Max. Voltage
19.0 ÷ 27.6V
Minimum output
voltage
19.0Vdc ±5%
Max current drawn
0.5A (FC501-L)
0.9A (FC501-H/FC501-HK)
Ripple 1%
Maximum internal
resistance of the
battery and
associated circuitry
1
W
Temperature range -5 to +40°C
Storage
Temperature
-40 to +80°C
Operating Humidity Up to 95% non-condensing
Dimensions
(W*H*D)
335*369*115 mm
Weight 3Kg(without batteries)
Table 10 FC501 Technical features