QUICK START-UP PROCEDURE
This procedure allows the quick start-up of the FC501
fire detection system.
When the loops are wired, electrically verified and all
the devices have been installed in to the loop, it is pos
-
sible to connect the loops terminals to the panel.
+
Before powering-on the Fire control panel, ensure
that the Earth Line has been connected.
PROCEDURE
1. At first panel power-on will start a FW procedure to
verify/program if some vital information for the User
Interface and for the panel, are programmed and
are consistent. These information are:
Ø Selected language
Ø Panel Identification number
Ø The panel Type (FC501-L/FC501-H)
Ø Installed batteries capacity (7Ah/12Ah/38Ah)
2. After have verified/programmed the previous data,
insert the date and time, see MODIFY Procedure
(User Manual). This step is important to guarantee
the Log file consistency.
At this point the panel will start the first system initializa
-
tion verifying the loops integrity, warming up the smoke
sensor circuitry, and the autoaddressing phase of the
devices, with the consequent search for no addressa
-
ble devices, and devices with the same address (see
procedure 1 Key Autoenrolling and Note on Autoad
-
dressing).
+
NOTE: The panel in this phase is configured to ma
-
nage closed loops (4 wires loop), if it is connected
to a spur (2 wires loop) it will generate broken loop
faults.
At the end of this first initialization phase the User Inter
-
face will be displayed at the main page with the capabi
-
lity to accept to the command and control functions.
3. Select the function Program pressing the key 1.
4. Insert the installer password (default=00000) every
digit will be masked by * symbol.
5. Choose the option by pressing the key 1.
The panel will start the enrolling procedure.
This procedure is divided into three main phases:
1 Auto-learning
2 Auto- addressing
3 Device Mapping
It is possible to stop the "AUTO" option at the end of
each phase; the results are different.
1 AUTO-LEARNING
In the first phase the panel looks for all the devices on
the loop already addressed (with the service tool).
During this phase, the panel will ask what pattern of au
-
tomatic assignment of zones shall be applied to found
devices (see Figure 57, 1B).
In the case of panel already configured, it indicates any
differences and asks how to proceed (see Figure 55,
1A), in which case the scheme of Automatic assig-
nment of the zones will be applied only to new devices
found.
If you stop the AUTO option at the end of this first pha-
se, see Figure 57 (A) will happen :
Ø The control panel will take over all devices with an
address between 1 and 128.
Ø The programming device at their default configuration.
Ø
Automatic assignment of labels.
Ø
Automatic assignment of the zones according to the
scheme chosen during that phase.
Ø
The output channels of the modules, sounders and
beacons will be enabled to active on fire alarm of the
assigned area (except in the case the zone auto-as
-
signment phase will not be chosen, accordingly all
the output channels of the modules, sounders and
the beacons will be activated for panel alarm.
Ø
The faults "NOT PROGRAMMING DEVICE" and
"wrong addresses" will be generated in the case of
not addressed devices or with address greater than
128, respectively.
+
If the enrolling result differs from the previously sto
-
red loop configuration a warning message will be
displayed and it is possible to reject the present en
-
rolling result, maintaining the previous configura
-
tion, or accept them.
+
The enrolling function will not be activated if there
are loop related faults present.
QUICK START-UP PROCEDURE 57