2 AUTO-ADDRESSING
The second phase will be started, if during Auto-lear
-
ning phase, not addressed devices have been identified
or have an address greater than 128. During this phase
all the not addressed devices will be detected. The pa
-
nel assigns them a temporary address and configure
them at default (see Figure 57, 2A).
If you stop the AUTO option at the end of this second
phase, see Figure 57 (B) will happen:
Ø
The auto assignment of the address to the not ad
-
dressed devices
Ø
The control panel will take over all devices
Ø
The programming devices to their default configura
-
tion.
Ø
Automatic assignment of labels.
Ø
Automatic assignment of zones based on a loop of
belonging.
58 Addressable Fire Panel FC501
AUTO ENROLLING
A
AUTO ADDRESSING
2/5 Temporary addresses assignment
RUNNINGAuto-Addressing
Wait please
1/5 devices searching
ESC to stop
3/5 Locate devices over the loops
4/5 1 minute preliminary polling
5/5 Devices inizialization
B
1C
2B
MAP. DEVICE
Auto-Addressing END
Addressed: 100 detectors
28 modules
ESC to exit ENTER to device Mapping
Device Mapping RUNNING 0= Stop
Evt time type counter: 102
101 12:55:58 CP L1
102 12:57:45 CP L1
1A
1B
2A
3A
STOPPED <= ResumeDevice Mapping
Evt time type add done 000:102
001> 12:55:58 CP L1 025<enter the Add.
002 12:57:45 CP L1
3B
ESC
Are you sure
to leave the device mapping proc. ?
ESC = No ENTER = Yes
C
0
FC501 Panel lev.3 :PROGRAM
1=Auto 2=Device 3=SW Zone 4=Output
5=Network 6=Map. Dev. 7=USB 8=System
9=Default 0=L3 PWD
3C
Not addressed devices found
start auto-addressing ?
Automatic zones assignment
1 = on loop basis
2 = on device address basis
3 = no assignment
Differences found!
2 Add new devices:
3 Discard changes:
1: Accept new configuration
ESC = no ENTER =yes
Figure 57 Programming option "AUTO"