Installing FC500IP board
The IP Module should be installed into the base of the
control Panel, as illustrated in Figure 13. Proceed as fol
-
lows:
!
Before installing the FC500IP Module, discon
-
nect control panel from its power supply (ma
-
ins and the batteries).
1. Open the control panel by unscrewing the two screws
4, then lift the cover from the bottom to separate it from
the backplate. Remove the fastening screw, figure 2,
item 22, between the motherboard and the backplate
and unlock the support of motherboard + User Interfa
-
ce, figure 2, item 9, using a flat screwdriver. Lift the con
-
trol board & display from the base.
2. Fix the IP Module on the base of the control panel
using the supplied screws 56.
3. Connect the connector 58 of the IP Module to the
connector 55b of the control panel using the supplied
flat cable 55. If you need to manage the control panel
ONLY/ALSO via IP, connect the connector 57a of the IP
module to the connector 55a of the control panel via the
supplied PC-Link cable 55c.
4. Connect connector 59 to the LAN using an Ethernet
cable.
+
Use a category 5 (or better) shielded Ethernet ca
-
ble (STP or FTP).
5. Re-fit the control board & display and secure with the
screw.
6. Reconnect the control panel to the power supply.
7. Program the IP Module as described in the section
“PC Programming” on page 29. For further information,
please refer to the dedicated manuals.
+
See page 29, paragraph “To connect the control
panel to a PC remotely”.
INSTALLATION 25
-10-5 0 5 101520253035404550
26,0
27,0
28,0
29,0
V
a)
27,4
22
Figure 12 Switching Power Supply Output Voltage graph. To find the Output Voltage using the graph: — indicate the
Probe temperature on the TEMPERATURE (°C) axis; draw a line from the temperature value point up to the curve a);
draw a line from the intersection point across to the VOLTAGE (V) axis; adjust the Output Voltage of the Switching Po
-
wer Supply to the resultant value. For example, if the Probe temperature is 22 °C, the Output Voltage of the Switching
Power Supply must be set at 27.4 V.
TEMPERATURE (°C) -10 -5 0 5 10 15 20 25 30 35 40 45 50
VOLTAGE (V) 29,0 28,8 28,6 28,2 28,0 27,8 27,6 27,2 27,0 26,8 26,6 26,4 26,2
Table 7 Switching Power Supply Output Voltage chart. To find the Output Voltage using the chart: — select the nea-
rest value to the Probe temperature on the TEMPERATURE (°C) row; read the respective value on the VOLTAGE (V)
row; adjust the Output Voltage of the Switching Power Supply to the indicated value. For example, if the Probe tempe-
rature is 22 °C, the Output Voltage of the Switching Power Supply must be set at 27.4 V.