FC490ST - Loop Service Tool
The FC490ST Loop Service Tool is used to program
the loop address into FC addressable devices. The
FC490ST displays information and performs tests on
devices. It has a 32 character backlit LCD alphanumeric
display, arranged in 2 rows of 16 characters and four
‘softkeys’, F1, F2, F3 and F4. Power for the FC490ST is
derived from 4 AA size nickel metal hydride rechargea
-
ble batteries. It may be run from an unregulated +12V
dc input ie, car cigarette lighter connection or 110/230V
ac mains adaptor, both of which will recharge the batte
-
ries as well.
FC410BDM - Beam Detector Module
The FC410BDM Beam Detector Interface Module is de
-
signed to interface FIRERAY 50 Beam Detectors to the
FC Digital Addressable Loop (it must not be used with
other types of beam detector). The FC410BDM moni
-
tors the Fire and Fault contacts and also monitors for
open and short circuits on the connections between the
interface and the beam detector. For remote siting of
the FIRERAY 50 an optional BTM800 Terminal Module
can be used with 4 core cable.
The FIRERAY 50 transmitter and receiver units are mo
-
unted in the same housing.
The FC410BDM Loop Powered Beam Detector Interfa-
ce Module is contained on a double sided printed circuit
board (PCB) which is fitted into a custom built fascia
plate with a protective cover being fitted over the PCB,
leaving only the connection terminals exposed. The fa-
scia plate is then fitted onto a standard dual-gang back
box with BESA fittings.
FC410CIM - Contact Input Module
The FC410CIM FC Addressable Contact Input Module
is designed to monitor fire contacts such as extingui
-
shing system control, ventilation control, fire door con
-
trol etc. The FC410CIM can be configured as:
Ø
Two spur circuits (Class B) monitoring multiple nor
-
mally open contacts, with short circuit giving a fault
output.
Ø
Two spur circuits (Class B) monitoring single nor
-
mally closed contacts, with short circuit giving a fault
output.
Ø
Two spur circuits (Class B) monitoring multiple nor
-
mally open contacts, with short circuit giving an alarm.
FC410DIM - Detector Input Module
The Addressable FC410DIM provides the ability to con
-
nect and Interface one or two zones of 24V dc 2-wire
conventional detectors (non-addressable) to the Fire
Alarm Controller.
The FC410DIM monitors the status of detectors and wi
-
ring to detectors and signals detector and wiring status
back to the Controller.
FC410RIM - Relay Interface Module
The FC410RIM Relay Interface Module provides one
volt-free relay changeover contact on a latching relay.
The relay is controlled by a command sent from the FC
fire controller via the addressable loop. The relay state
(activated, deactivated or stuck) is returned to the con
-
troller.
FC400CH - Addressable Carbon Monoxide
+ Heat Detector
The FC400CH carbon monoxide plus heat detector forms
part of the FC400 Series Addressable Fire detectors.
The detector is intended to plug into the following:
Ø
5B 5” Universal Base.
Ø
FC450IB 5” Isolator Base.
Ø
FC430SB Low Power Sounder Base.
Ø
FC430LPSB Loop Powered Addressable Sounder
Base.
Ø
FC430LPASB Loop Powered Addressable Soun
-
der/Beacon Base.
The detector is designed to transmit, to a remote Fire
Class controller, digital signals which represent status
of the carbon monoxide and heat elements of the detec
-
tor. Software within the controller is used to interpret the
returned carbon monoxide and heat values to raise
alarm or other appropriate response according to the
type of detector configured in Fire Class Console.
801RIL - Remote LED Indicator
The 801RIL Remote Indicator is used where a detector
LED is not visible ie, when the detector is mounted in a
roof void, lift shaft etc.The 801RIL is mounted to a single
gang electrical box and is supplied with 2 x M3.5 screws.
801HL - Remote LED Indicator
The 801HL Remote Indicator is used where a detector
LED is not visible ie, when the detector is mounted in a
roof void, lift shaft etc.
The 801HL provides a larger indicator for use in place of
the 801RIL when longer distances are involved or in
VdS influenced markets.
The 801HL can be mounted to any suitable flat surface
and has fixing centres at 60 and 80mm.
HVR800-High Voltage Relay
The HVR800 High Voltage Relay Interface is a non-ad
-
dressable multi-voltage relay module (operating from
24V dc, 24V ac, 120V ac and 240V ac).
The encapsulated HVR800 provides a 10 amp volt-free
contact that can be used to extend the contact ratings of
FC410RIM Addressable Relay Module applications.
A maximum of four HVR800s can be individually driven
and controlled by an FC410MIO Small Addressable
Multi-Input/Output module if all HVR800s are powered
by 120V ac or 240V ac. For ac operation, no external dc
power supply unit is required to operate the relay.
When used to switch 24V dc, the HVR800 must be pro
-
vided with an external 24V dc supply which should be
switched through the clean relay contacts of an
FC410MIO or FC410RIM.
ACCESSORY 65