3 KEY - SW zone
The SW zone option in the PROGRAMMING menu ac
-
tivates the screen used to select and program the Sof
-
tware zone (see figure 44).
The Alphanumeric keypad The Alphanumeric key
-
pad is used to select the zones number (ID).
Cursor Keys
No function is related to UP and Down
Keys.
The Right key to selects the next available SW zone.
The Left key to selects the previous available SW zone.
ESC key
The ESC key deletes the procedure and re
-
turns to the previous page;
ENTER Key Accept the SW zone selection and acti
-
vate the loop device programming page, if the SW zone
exists, otherwise a warning page is displayed for 5s
"WRONG VALUE! enter the parameter again".
After 5s the User Interface moves back to the choose
SW zone pages.
n
SW zone in WALK TEST
After selecting the SW Zone, you will be able to enable or
disable the option Zone in WALK TEST (OFF) or not (off);
Ø
if the option all (ALL) is selected , all the devices assi
-
gned to zones in WALK TEST mode, will NOT gene-
rate alarm in the case of their activation but they will
reach the TEST status.
Ø If the option det (DET) is selected , only the detectors
assigned to zones in WALK TEST mode, will NOT
generate alarm in the case of their activation but will
reach the TEST status.
Ø If the option cp (CP) is selected , only the call-points
assigned to zones in WALK TEST mode, will NOT
generate alarm in the case of their activation but will
reach the TEST status.
The presence of a zone in WALK TEST mode is si
-
gnalled by the TEST yellow LED on the User
Interface. More than one zone can be put in WALK
TEST mode at the same time.
Cursor Key
No function is related to UP and Down Keys.
Right key: selects the following ON -OFF-ALL-det-cp.
Left key: selects the previous ON-OFF-ALL-det-cp.
ESC Key
ESC key deletes the procedure and returns
to the programming page.
ENTER key The ENTER key accepts the selection
and activates the corresponding programming page
n
Detector alarm verification (Smoke delay)
For each zone, it is possible to program the delayed ac
-
tivation of smoke detectors, according to the following
schedule:
when the smoke level exceeds the alarm threshold, the
panel does not signal anything at first;
- after 60 seconds if the smoke level is still above the
threshold, the system goes into alarm condition, other
-
wise there are no signals;
- within 30 minutes, a new alarm or activation of another
sensor in the same zone causes the alarm of fire panel.
To program the delay on the activation of smoke detec
-
tors, from Programming menu: SW Zone (KEY 3).
- After selecting the SW Zone, on the subsequent di
-
splay about the zone to test, select OFF and press
Enter.
- on the fsubsequent display about the new option “De
-
tector alarm verification”, select ON (to enable) and
press Enter. In this phase:
Cursor Keys
No function is related to Up and Down
keys.
Use the Right and Left keys to select: On-OFF.
ESC key
Use the ESC key to delete the operation and
to step back to previous page.
ENTER key
Use the ENTER key to accept the selec-
tion and activate the programming page.
n
Prealarm
For each zone, it is possible to program the activation of
a common pre-alarm delay ( 10 min.). The procedure is
PROGRAMMING FROM THE PANEL 51
FC501 Panel lev. 3: PROGRAM
SC Output: 001
Control Panel name
Access Level
Outputs type
Output
Number
SC Output 001 ev.l 3 :PROGRAM
[]
OUTPUT NAME
Insert Output label
Up or Down to select the type
Enter the SC Output number
Control panel
Status
Access Level
Control panel
Status
Output
Number
Enter the parameter again
WRONG VALUE!
If blinking
the panel works
properly
Figure 46 Pages for programming "SC active on disa
-
blements" option.
FC501 Panel lev. 3: PROGRAM
SC Output: 001
Control Panel name
Access Level
Outputs type
Output
Number
SC Output 002 ev.l 3 :PROGRAM
[]
^
OUTPUT NAME Master Panel
Insert Output label
Up or Down to select the type
Enter the SC Output number
Control panel
Status
Access Level
Control panel
Status
Output
Number