In each case at the end of the device Mapping phase
(see Figure 57, C) a check is performed to detect the
presence of "doubles addresses"; in this case the invol
-
ved addresses will be indicated and it will not be possi
-
ble to abandon the procedure until the complete
removal of the error condition.
+
The procedure for the devices mapping can also be
launched outside the AUTO function,by activating
the programming function called "localization. (Key 6,
on the PROGRAM status) that allows to activate the
procedure for devices mapping on demand, on a
system already configured and without the need to
proceed to their activation. It is meant to correct er
-
rors or change the system "on the run" and use all the
features and capabilities described above.
System default
n
Zone assignment
To mimic a conventional panel the acquired device over
the loops will be automatically assigned to a predefined
zone. Two different scenarios are possible:
Exit at the end of the Auto Addressing phase without
executing the Device Mapping process, in this case:
Ø all the devices located on loop #1 will be assigned to
zone #1
Ø all the devices located on loop #2 will be assigned to
zone #2
Ø all the devices located on loop #3 will be assigned to
zone #3.
At the end of the Device Mapping process.
The device address to zone assignment scheme is the
follow:
Ø
From address 01 to address 16 assigned to
zone #1
Ø
From address 17 to address 32 assigned to
zone #2
Ø
From address 33 to address 48 assigned to
zone #3
Ø
From address 49 to address 64 assigned to
zone #4
Ø
From address 65 to address 80 assigned to
zone #5
Ø
From address 81 to address 96 assigned to
zone #6
Ø
From address 97 to address 112 assigned to
zone #7
Ø
From address 113 to address 128 assigned to
zone #8
If an address is not manually assigned to a device ( eit
-
her via FC490ST or during the device mapping phase)
no zone will be assigned to it.
The previous zone assignment schemes are applied
also to the first "trigger zone" in the case of output only
devices(sounder, beacon, SNM module,…) or output
channel of Input/output devices.
+
Note that in the case of none zone assigned, the
output channel trigger event is the panel alarm.
n
System default parameters
Temperature detector default values
Label See note (**)
Enablement Enabled
Led blink On
Assigned zone (see: "Zone assignment)
Base type Normal
Use zone setting Yes
Day operating mode A2S
Night operating mode A2S
Smoke detector default values
Label See note (**)
Enablement Enabled
Led blink On
Assigned zone (see: "Zone assignment)
Base type Normal
Use zone setting Yes
Day smoke sensitivity Medium
Night smoke sensitivity Medium
Smoke+Temperature detector default values
Label See note (**)
Enablement Enabled
Led blink On
Assigned zone (see: "Zone assignment)
Base type Normal
Use zone setting Yes
Day temp. operating mode A2S
Day smoke operating mode normal
Day smoke sensitivity Medium
Night temp. operating mode A2S
Night smoke operating mode normal
Night smoke sensitivity Medium
CO + Temperature detector default values
Label See note (**)
Enablement Enabled
Led blink On
Assigned zone (see: "Zone assignment)
Base type Normal
Use zone setting Yes
Day temp. operating mode A2S
Day CO operating mode normal
Day CO sensitivity medium
Night temp. operating mode A2S
Night CO mode normal
Night CO sensitivity medium
60 Addressable Fire Panel FC501