CO+Smoke+Temperature detector default values
Label See note (**)
Enablement Enabled
Led blink On
Assigned zone (see: "Zone assignment)
Base type Normal
Use zone setting Yes
Day algorithm Universal
Night temp. operating mode Universal
Modules default values
Label See note (**)
Enablement Yes
Led blink On
Activation unit (where applicable) Off
Act as SC1 (where applicable) Off
Input Channels
Enablement Yes
Channel Label See note (**)
Assigned zone Address related
(see: "Zone assignment)
Operating mode Style C, NO
Use zone setting Yes
Output Channels
Enablement Yes
Channel label See note (**)
Trigger zone #1 Address related
(see: "Zone assignment)
Trigger zone #2 None
Trigger zone #3 (where applicable) None
Trigger zone #4 (where applicable) None
Trigger point #1 None
Trigger point #2 None
Trigger point #3 None
Silenceable Yes
Active on disablement (where applicable) Off
Trigger on event Zone Alarm
Delay from alarm Off
Silenceable Yes
Sounder pattern (where applicable) 7Hz fast sweep
Sounder volume (where applicable) high
Beacon enablement (where applicable) Yes
Beacon flash rate (where applicable) 0.5 Hz
DDM module default values
Label See note (**)
Enablement Enabled
Led blink On
External power On
Detector type 4/20 mA Source
Threshold set Set #1
Input Channels
Enablement Enabled
Channel Label See note (**)
Assigned zone Address related
(see: "Zone assignment)
Use zone setting Yes
TSM module default values
Label See note (**)
Enablement Enabled
Led blink On
External power On
Input function Door monitoring
Loop monitoring Off
Door monitoring event Fault
Monitoring time 30s
Input Channel
Enablement Enabled
Channel Label See note (**)
Assigned zone Address related
(see: "Zone assignment)
Operating mode Style C, NO
Output channel
Enablement Yes
Channel label See note (**)
Trigger zone #1 Address related
(see: "Zone assignment)
Trigger zone #2 None
Trigger point #1 None
Trigger point #2 None
Trigger point #3 None
Silenceable Yes
Trigger on event Zone Alarm
Delay from alarm Off
Zones default values
Label Zone AAA(*)
Enablement Enabled
Walk test Off
Detector warning Off
Delay to alarm Off
Drift compensation Off
Double knock Off
Smoke verification Off
Delay to alarm duration 0s
On board programmable outputs default values
Enablement Yes
Channel label tttt y(****)
Trigger zone #1 none
Trigger zone #2 None
Trigger zone #3 None
Trigger zone #4 None
QUICK START-UP PROCEDURE 61