Access to Signalling and Commands
There are 4 access levels, in compliance with the Fire
Safety Regulations in force.
Access Level1 (L1)
Viewing: ALL persons can view
the Control panel status (No Password requested).
Access Level 2 (L2) Operating the system (PIN Code
entered): Password Code Users can operate the
system (User level).
Access Level 3 (L3) Programming and Opening the
Control panel (Password Code entered): ONLY Quali
-
fied persons with authorization are allowed to open
the Control panel door (requires removal of the Cover
screws) for maintenance purposes or to replace batte
-
ries. (Installer Level).
Access Level 4 Repairing or replacing the PCB:
ONLY the Manufacturer should be allowed to repair or
replace the PCB, (requires removal of the Cover
screws).
n
Users and Installers Features
The panel will be able to recognize and manage up to 8
different users and 2 different installers. At each login of
any users will be logged the login event with the ID of
the user. At each login of any installers will be logged
the login event with the ID of the installer. It will also log-
ged the return to access level 1 of the panel to indicate
the end of the user or installer session.
In the following the default Password for the eight Users.
USER #1 11111
USER #2 22222
USER #3 33333
USER #4 44444
USER #5 55555
USER #6 66666
USER #7 77777
USER #8 88888
In the following the default Password for the two Installers:
INSTALLER #1 00000
INSTALLER #2 99999.
By default only the USER #1 is working with its default
password. All the other users are not available and not
enabled. The USER #1 may not be disabled or made
unavailable.
By default only the INSTALLER #1 is working with its
default password. All the other installers are not availa
-
ble and not enabled. The INSTALLER #1 may not be di
-
sabled or made unavailable.
Only the INSTALLER #1,via Fireclass Console or panel
User Interface, may modify the availability and enabling
status of the USERs #2.... #8 and INSTALLER #2.
The INSTALLER #1, via Fireclass Console or panel
User Interface, may modify the password value for the
USERs #1.... #8 and INSTALLER #2.
+
Each Installer o each User can modify its own
password.
When the first password is entered via User Interface by
INSTALLER #1 to a User/Installer, it will be declared as
"available" and will be automatically enabled.
If the first installer lost the password, it is possible to en
-
ter a new password using the following procedure:
- open the fire panel after removing the two screws (ac
-
cess level 4) and remove the jumper J5 of the main bo
-
ard,
- access to the installer menu page,
- go to programming page of the installer password and
enter the new password,
- now the new password is stored as the current
INSTALLER #1, the user interface will return back to the
MAIN page indicating an activity of local programming,
followed by a panel reset,
- replace the J5 jumper to restore the normal program
menu page functionality (see Figure 40 b).
n
Power Supply
The power supply system of the FC501 Control panels
complies with EN54-4.
All models are powered by the Mains (230V, 50 Hz):
Ø
the FC501-L has Switching Power Supply which
supplies up to 1.5 A at 27.6V;
Ø
the FC501-H has Switching Power Supply which
supplies up to 2.5 A at 27.6V;
Ø the FC501-HK has Switching Power Supply which
supplies up to 2.5 A at 27.6V;
All models can house two 12V batteries which, when
connected in series, will supply 24V to the Control panel
and peripherals in the event of black-out.
The FC501-L can house two 12V, 7Ah batteries
(YUASA NP or 12V 12Ah FR model or similar flame
class UL94-V2 or higher).
+
If necessary, (full configured Loop or for particular
requirements of the system) the FC501-H and
FC501-HK control panel can be connected to two
12V, 38 Ah batteries in an external metal box (see
Figure 14).
This Control panel can detect, signal and store in me
-
mory the following power faults: shorted 24A or 24R
outputs; Low battery, Battery fault or Battery discon
-
nected Battery trouble LED ( ), Ground fault Earth
LED ( ) and Mains failure Power Supply Fault LED
().
+
The Battery or Low Battery fault may be signal
-
led with a delay up to 1 minute (see Table n.1). The
Mains (Amber) fault will be signalled when the
programmed delay expires.