Use the 1 Key to select Auto option, the display will
show the Figure 41: in this phase:
Alphanumeric keypad No function is related to
Alphanumeric keypad.
Cursor Keys
No function is related to UP, Down,
Right, Left Key;
ESC Key
Use ESC key to cancel the operation and to
step back to MAIN page.
ENTER key
No function is related to ENTER key.
n
Automatic zones assignment
After few seconds: the panel will prompt to choose the
type of automatic zones assignment.
+
This feature allows to assign the zone to each enrolled
detector, and define the first trigger zone for the activa
-
tion of all outputs channels in the enrolled modules.
The possible schemes used to assigned the zones are
proposed to the installer by the panel during the enroll
process (see Figure 41d):
1 = on Loop basis
2 = on device address basis
3 = no assignment.
Three different schemes are possible:
Scheme 1): all the devices located on loop1 will be assi
-
gned to zone 1; all the devices located on loop 2 will be
assigned to zone 2; all the devices located on loop 3 will
be assigned to zone 3.
Scheme 2)
From address 01 to address 16 assigned to zone 1
From address 17 to address 32 assigned to zone 2
From address 33 to address 48 assigned to zone 3
From address 49 to address 64 assigned to zone 4
From address 65 to address 80 assigned to zone 5
From address 81 to address 96 assigned to zone 6
From address 97 to address 112 assigned to zone 7
From address 113 to address 128 assigned to zone 8.
Scheme 3)
All the devices found all over the loop are assigned to
zone #0 (system zone).
+
The previous zone assignment schemes are ap
-
plied also to the first "trigger zone" in the case of
output only devices (sounder, beacon, SNM modu
-
le) or output channel of Input/output devices.
After the Zones assignment is selected
+
For devices already addressed (1-128) the zone
assignment procedure is that explained above
(see Figure 42d). For not addressed devices, if you
choose ESC at the end of Auto addressing, the pa
-
nel assigns the zone based on the loop, but if you
choose ENTER the panel assigns the zone based
on its address (see table on page 57, 58, 59)
In this phase, the Alphanumeric Keypad only is active:
Alphanumeric keypad used to select the appropriate
zone assignment scheme 3.
n
Warning Enrolling (Autolearning)
When there are some differences between the present
configuration and that of the Enrolling (Autolearning) re
-
sults, the display will show the Figure 40b: in this phase:
Alphanumeric keypad
1 = delete the old configura
-
tion and accept the new one;
2 = To accept only the differences between the new and
the previous configuration detected. The new devices
will be added, while the devices that are no longer pre
-
sent will be removed. This applies both to the loop devi
-
ces and 485 network devices;
3 = The current configuration, detected, will be discar
-
ded, the previous configuration will still be valid.
Cursor Keys
No function is related to UP, Down,
Right, Left Key;
ESC Key
Use ESC key to cancel the operation and to
step back to MAIN page.
ENTER Key
The ENTER key activate the device de
-
tails page
. The fields “Loop1”, “Loop2" and ”Loop3"
show if there are any devices connected. In both cases:
Autoscan OK or NO, it is possible to view details on the
Loop, Figure 41c). The “RS485net: Rep“ show the
number of repeaters found on the network RS485.
In this phase:
Cursor Keys
The UP key: shows information relating
to the next Loop;
The Down Key: shows the information relating to the
previous Loop;
No function is related to Right and Left Keys.
ESC Key
Use ESC key to cancel the operation and to
step back to MAIN page.
PROGRAMMING FROM THE PANEL 47
FC501 Panel lev.3: PROGRAM
ENT to view details
List of Loop with the resultpresent autoscan
Loop1=OK Loop2=OK Loop3=OK
Differences found!
b)
2 Add new devices:
3 Discard changes:
Loop= 01 lev.3: PROGRAM
Modules : 125
ENT to program devices
Num. analyzed Loop
ILoop=073 mA (400ma max)
Value of the current in the three loops,
in real time, (data are updated )every 5s
Detectors: 125
Num. detectorsfound
c)
Num.of
found modules
FC501 Panel lev.3: PROGRAM
ENROLLING IN PROGRES
a)
N.B. If the Enrolling phase finds page will be shown,
otherwise the page b)
differences, the following
PLEASE WAIT
1: Accept new configuration
Rs485net: REP.=4
Access Level
I
f
blinking
control panel
working properly
Control panel status
Control Panel name
If blinking
control panel
working properly
Control panel status
Access Level
Control Panel name
Access Level
Control panel status
If blinking
control panel
working properly
Automatic zones assignment
1 = on loop basis
2 = on device address basis
3 = no assignment
d)
Figure 41 Autoscan results window