If for requirements of the system, the installer wants to
set the system:
example set the address 1 to detector 1, address 2 to
detector 2, and so on:
Ø
press the ENTER key, so the fire panel initiates the
MAPPING DEVICES phase. First phase:
Ø
In this phase, the installer must activate in sequence,
moving in the plant, all input devices: detectors, in
-
put modules, Manual Call Point, and then return in
front of the fire panel.
Ø
Report the sequence of activation on the map of
system.
The fire panel will store the activation sequence
(even temporarily).
The installer using the User Interface UP and DOWN
key will start to examine the first activated device.
Ø
Select the device, the address will blink, so the instal
-
ler can change the address.
Press ENTER to confirm. At this point the address
will became fixed.
+
If the ENTER key is pressed again, the installer
can switch to programming phase of the device in
question.
"Unique”, indicates that it is the only device of it’s type
on the loop. So it is not necessary to activate it, the in
-
staller knows where it is.
Second phase:
In this phase, the installer examines the sounders,the
beacons and the output module.
Ø When the installer, scanning the list of previously
auto-addressed devices, reaches an output-only de-
vice type, this device becomes active (a sounder
starts to sound, a beacon starts to flash, an output
module illuminates its LED) until a new device is se-
lected or the permanent address is entered.
In this way it is possible to locate where the device is.
+
The enroll process doesn’t take place until all loop
wiring trouble have been removed.
+
The auto-addressing procedure have to be used
when on the loop there are NG1 devices, otherwise
it doesn’t have effect.
+
The device mapping process doesn’t take place
until all double address faults have been removed
2 KEY -Device
The Device option in the PROGRAMMING menu acti
-
vates the screen used to select and program the devi
-
ces on the loops (see figure 43);
n
Choose the Loop (see User Manual View Devices)
In this phase:
Alphanumeric keypad No function is related to the
Alphanumeric keypad.
PROGRAMMING FROM THE PANEL 49
FC501 panel lev 3: PROGRAM
Master Panel
[L1]L2
Choose loop Loop 1
Name
selected
loop
FC501 Panel lev 3 : PROGRAM
FC501 Panel
d001 [d187] m250
Programmed
address
Loop 1
Add=<123>
400PH
Selected address Selected device
MS:L1 det001 lev 3 : PROGRAM
FC501 Panel
Detector
to program
[Temperature]
Device name
Parameter to program
Name of
Control Panel
Control panel
Status
Access Level
I
f
blinking
the panel works
properly
Detector
MS:L1 det001 lev 3 : PROGRAM
FC501 PanelREMOVE DEVICE?
Select
NO yes
^
Figure 43 Pages of Selecting and programming Devi
-
ces on Loop
Heat
detector
Smoke detector
Smoke +
Heat detector
Heat+Smoke +
CO detector
Working mode:
DAY:
Working mode:
DAY:
Working mode:
DAY:
CR
A1R
A2S
Temp= A2S
A1R
DIS
High Immunity
Universal
Detector label Detector label Detector label Detector label
Assigned zone Assigned zone Assigned zone Assigned zone
Callpoint DDM Module
Detector type
Channel to
program
Callpoint label Module label
CNV conventional
GSI 4-20 mA sink
GSO 4-20 mA source
Generic digital
output channel
(loop devices)
DDM input channel
Working mode:
BNO
CNO
CNC
Input label Output label
Assigned Zone Trigger Zone # 1
Trigger Zone # 2
Trigger Zone event
ALA Alarm
DLY Delay to alarm
WAR warning
FAU fault
TST Test
DK Double Knock
Channel to
program
Generic digital
input channel
(loop devices)
Input label
Assigned Zone
Detector base
Standard
Isolator
Relay
Sounder
Addressable
Detector base
Standard
Isolator
Relay
Sounder
Addressable
Detector base
Standard
Isolator
Relay
Sounder
Addressable
Heat +
CO detector
Working mode:
DAY:
Enhanced
Disabled
CO=Default
Detector label
Assigned zone
Detector base
Standard
Isolator
Relay
Sounder
Addressable
Remove device?
Yes
No
Remove device?
Yes
No
Remove device?
Yes
No
Remove device?
Yes
No
Remove device?
Yes
No
Working mode:
NIGHT:
Working mode:
NIGHT:
Working mode:
NIGHT:
CR
A1R
A2S
Temp= A2S
Default
A1R
DIS
Smoke=
Enhanced
Disable
High Immunity
Universal
Working mode:
NIGHT:
Enhanced
Disabled
CO=Default
Working mode:
DAY:
Smoke=
Enhanced
Disable
Default
Working mode:
DAY:
Temp= A2S
A1R
DIS
Working mode:
NIGHT:
Smoke=
Enhanced
Disable
Default
Working mode:
NIGHT:
Temp= A2S
A1R
DIS
Generic Module
Remove device?
Yes
No
Remove device?
Yes
No
Remove device?
Yes
No
Module label
Assigned zone
Silenceable
On
Off
Trigger Zone # 3
Trigger Zone # 4
Trigger Point # 2
Trigger Point # 1
Trigger Point # 3
Table 9 Values table of the programming devices
Note: The underlined options are the default options.