Allows a voice message to be recorded via the mi
-
crophone on the PC (max 6 sec., Header message 12
sec.).
Allows to import an audio file (mp3, wav) to be used
as a voice message (max 6 sec.).
+
The USB memory stick is the ONLY way to downlo
-
ad in the panel the AUDIO files
IP interface
The IP interface section is active after the
module FC500IP has been enabled in the General
Options page (Figure 27). The IP module programming
is in 3 sections: OPTIONS, ADDRESS BOOK and
ADVANCED.
OPTIONS:
DHCP – Select this option if you wish to use a dynamic
address for the IP Module you are programming.
- IP static– Select this option if you wish to assign a sta
-
tic IP address to the IP Module you are programming,
then set the following parameters:
- IP address: enter the IP address to be assigned to the
IP Module; the network administrator will provide you
with this information. The default setting is
192.168.0.101.
- Subnet mask: this must be the same as the subnet
mask for the local network; only one subnet mask is va-
lid for each local network. All nodes on the same subnet
will use the same subnet mask; the network administra-
tor will provide you with this information. The default
setting is 255.255.0.0.
- Gateway IP address: enter the IP address of the local
gateway which may be used by the IP Module to connect
to a PC outside the LAN (WAN). The default setting is
0.0.0.0.
Ethernet speed
This section is used to set the parameters correspon-
ding to the Ethernet interface of the IP Module: the Auto
setting is selected by default.
Ø
Auto – If this option is enabled, the IP Module will
take the speed and duplex values from the network.
If this option is disabled, the speed and duplex valu
-
es must be set as described below.
Ø
Speed – If the Auto option is disabled, set the speed
value as appropriate: 10 Mbps or 100 Mbps.
Duplex – If the Auto option is disabled, set the
Data exchange (Duplex) mode as appropriate:
Half or Full.
Read-only options
The values in this section cannot be modified.
They display information relating to the connected
IP Module.
Ø
MAC Address – Displays the MAC address of the
IP Module: the MAC address is a unique identifica
-
tion number assigned to every IP device throughout
the world.
Ø
Firmware version – Displays the version of the
program running on the IP Module.
Ø
Boot version – Displays the boot version.
Current IP address – Displays the IP address as
-
signed to the IP Module.
General options This section is used to select the
general options for the IP Module.
Encryption key – If it has been programmed, the IP
Module will use this key to encode and decode the pac
-
kets exchanged with the PC. The encryption key may
include between 1 and 32 hexadecimal characters
(numbers 1 to 9 & letters A to F). To disable encryption,
enter 0 (zero). If the encryption key does not corre
-
spond to that of the IP Module, communication between
the PC and the IP Module will NOT be permitted. The
default setting is 0 (encryption key not enabled).
Board port – This is the port which should be used to
communicate with the IP Module. The default setting is
3064.
Pass Through port – This is the port which should be
used to communicate with the control unit. The default
setting is 3062.
Board code – This code should be applied when the Fi
-
reClass Console is used to program the IP Module, eit
-
her remotely or locally. The code should consist of 4
hexadecimal digits. The default setting is 5555.
Idle Connection Timeout – Enter the maximum time pe
-
riod during which no data is transmitted before the connec
-
tion is terminated. The default setting is 20 seconds.
ADDRESS BOOK
Account Code – The account number is used by the
central station to distinguish between transmitters. The
-
re is one account number programmable for the
FC500IP. Default value: (0000FFFFFF).
+
Account codes 0000FFFFFF,FFFFFFFFFF and
0000000000 are not valid accounts.
Ø Supervision-To enable Supervision mode, tick this option.
Main
Ø IP_Address – Static IP address for the receiver. Pro-
gram the IP address of the central station receiver. If an
IP receiver is not connected program 0.0.0.0 address.
Default value: 000.000.000.000.
Ø
Local Port and Remote Port – These values show the
ports to communicate with receiver. The same recei
-
ver supplies these values. Default values:3060 (Local
Port) and 3061 (Remote Port).
Backup
Ø
Receiver IP – Static IP address for the second recei
-
ver. Program the IP address of the second receiver.
Default value: 000.000.000.000.
PC PROGRAMMING 39
Figure 30 Example of the graphical maps