EasyManuals Logo

Flintec DAD143 Series User Manual

Flintec DAD143 Series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
DAD 143.x User Manual Profinet Rev.1.1.1 March 2023 Page 25 of 95
Menu 8 Data Communication / Continuation
8
Data Communication setup (Menu 8.6 to 8.9)
8.6
Gateway Address, depending on protocol* (use the UP/DOWN buttons)
8.6.y
ProfiNet (factory default), for INSPECTION via front panel, only:
8.6.1
Setting
000192
8.6.2
Setting
000168
8.6.3
Setting
000001
8.6.4
Setting
000254
8.7
Select the addressing mode* (use the UP/DOWN buttons)
ProfiNet
not in use:
8.8
Protocol Selection for Port 1 & 2 (use the UP/DOWN buttons)
ProfiNet
Ethernet/IP
EtherCAT
Modbus TCP
Remark: changing the protocol - the DAD 143.x!
8.9
Save or Restore user setup (use the UP/DOWN buttons) (commands SU / RU)
STORE Store setup in EEPROM
RECALL Restore setup from EEPROM
Remark: After RECALL, for activation you have to re-start the DAD 143.
*Notes for the different protocols:
- ProfiNet IO: Menu 8.4.y, 8.5.y and 8.6.y can be used for inspection, only. Read the IP address, the
network mask and the default gateway address. Change settings via front panel is permanent locked!
Menu 8.7 is not in use - - - - - - .
Note: The 3 network addresses and the station name are set by use of special ProfiNet interface
commands and can only be set by calling dedicated ProfiNet interface functions.
- Ethernet/IP: Menu 8.4.y, 8.5.y and 8.6.y can be used for inspection and setting of the IP address, the
network mask and the default gateway address. Settings of these values will make sense only if
STATIC addressing is selected in menu 8.7.
- EtherCAT: Menu 8.4.y, 8.5.y and 8.6.y are not using IP addresses. These settings have no meaning for
------ for these menu settings.
In menu 8.7 select a device identification number between 0 and 65535.
- Modbus TCP: Menu 8.4, 8.5 and 8.6 can be used for inspection and setting of the IP address, the
network mask and the default gateway address. Settings of these values will make sense only if
STATIC addressing is selected in menu 8.7.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flintec DAD143 Series and is the answer not in the manual?

Flintec DAD143 Series Specifications

General IconGeneral
BrandFlintec
ModelDAD143 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals