Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14
flowserve.com
For a Group 2 Only device it means that the device is allocated to a Master.
For a UCMM capable device it means that the device has one or more established connections.
“CONN TIMEOUT” = One or more I/O Connections are in the Timed-Out state.
“COMM FAULT” = Failed communication device. The device has detected an error that has rendered it incapable of
communicating on the network (Duplicate MAC ID, or Bus-off).
“ID COM FLT REQ” = A specific Communication Faulted device. The device has detected a Network Access error and
is in the Communication Faulted state. The device has subsequently received and accepted an Identify Communication
Faulted Request. Long Protocol message.