Number of inputs - PV 1 2
Number of inputs - PV 2 1
Max. capacity of the PV generator
against earth
1600 nF
Insulation resistance test limit value
between PV generator and earth (on
delivery)
10)
100 kΩ
Adjustable range of insulation resist-
ance test between PV generator and
earth
9)
10 - 10000 kΩ
Limit value and tripping time of the
sudden residual current monitoring
(on delivery)
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
Limit value and tripping time of the
continuous residual current monitor-
ing (on delivery)
300 / 300 mA / ms
Adjustable range of continuous resid-
ual current monitoring
9)
30 - 300 mA
Cyclic repetition of the insulation res-
istance test (on delivery)
24h
Adjustable range for the cyclic repeti-
tion of the insulation resistance test
-
DC input data battery
8)
Max. voltage 531 V / 700 V *
* only with suitable disconnection
device between inverter and battery in
the event of a fault
Min. voltage 160 V
Max. current 22 A
Max. output 8000 W
DC inputs 1
AC input/output data
Rated power (P
nom
) 8000 W
Max. output power 8000 W
Rated apparent power 8000 W
Nominal mains voltage 3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V
Min. mains voltage
154 V
1)
Max. mains voltage
280 V
1)
Max. output current 16.4 A
Nominal output current (at 230 V) 11.6 A
Current (inrush)
6)
9.9 A / 4 ms
Nominal frequency
50 / 60 Hz
1)
164