9.1 Function Code Tables
9-3
Chap. 9 FUNCTION CODES
The following tables list the function codes available for the FRENIC-Mini series of inverters.
F codes: Fundamental Functions
Code Name Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
(Note)
Refer
to
page:
F00 Data Protection 0: Disable both data protection and digital
reference protection
– – Y Y 0
1: Enable data protection and disable digital
reference protection
2: Disable data protection and enable digital
reference protection
3: Enable both data protection and digital
reference protection
F01 Frequency Command 1 0: UP/DOWN keys on keypad N Y 4
1: Voltage input to terminal [12] (0 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA
DC)
3: Sum of voltage and current inputs to
terminals [12] and [C1]
4: Built-in potentiometer (POT)
7: Terminal command UP/DOWN control
9-20
F02 Operation Method 0: RUN/STOP keys on keypad (Motor
rotational direction specified by terminal
command FWD/REV)
– – N Y 2
1: Terminal command FWD or REV
2: RUN/STOP keys on keypad (forward)
3: RUN/STOP keys on keypad (reverse)
9-21
F03 Maximum Frequency 1 25.0 to 400.0 0.1 Hz N Y ACU:60.0
E:50.0
9-22
F04 Base Frequency 1 25.0 to 400.0 0.1 Hz N Y AU:60.0
CE:50.0
F05 Rated Voltage at Base
Frequency 1
0: Output a voltage in proportion to input
voltage
1 V N Y2
80 to 240: Output an AVR-controlled voltage
(for 200 V class series) *4
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
ACE:0
U:230/460
F06 Maximum Output Voltage
1
80 to 240: Output an AVR-controlled voltage
(for 200 V class series) *4
1 V N Y2
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
A:220/380
C:200/380
E:230/400
U:230/460
F07 Acceleration Time 1 0.00 to 3600 0.01 s Y Y 6.00
Note: Entering 0.00 cancels the acceleration
time, requiring external soft-start.
F08 Deceleration Time 1 0.00 to 3600 0.01 s Y Y 6.00
Note: Entering 0.00 cancels the deceleration
time, requiring external soft-start.
9-24
F09 Torque Boost 1 0.0 to 20.0
(percentage with respect to "F05: Rated
Voltage at Base Frequency 1")
Note: This setting takes effect when F37 = 0, 1,
3, or 4.
0.1 % Y Y See
Table A.
F10 1: For a general-purpose motor and Fuji
standard permanent magnet synchronous
motor with shaft-driven cooling fan
– – Y Y 1 9-27
Electronic Thermal
Overload Protection for
Motor 1
(Motor characteristics)
2: For an inverter-driven motor with separately
powered cooling fan
F11 (Overload detection level) 0.00: Disable, 0.01 to 100.0
1 to 135% of the rated current (allowable
continuous drive current) of the motor
0.01 A Y Y1
Y2
See
Table A.
F12 (Thermal time constant) 0.5 to 75.0 0.1 min Y Y 5.0
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).
*4 The setting for the 200 V class series applies also to the single-phase 100 V class series.