9-4
(F code continued)
Code Name Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
(Note)
Refer
to
page:
F14 0: Disable restart (Trip immediately) Y Y 9-30
Restart Mode after
Momentary Power Failure
1: Disable restart (Trip after a recovery from
power failure)
(Mode selection) 2: Trip after decelerate-to-stop *2
4: Enable restart (Restart at the frequency at
which the power failure occurred, for general
loads)
AC:1
EU:0
5: Enable restart (Restart at the starting
frequency)
F15 Frequency Limiter (High) 0.0 to 400.0 0.1 Hz Y Y 70.0 9-34
F16 (Low) 0.0 to 400.0 0.1 Hz Y Y 0.0
F18 Bias
(Frequency command 1)
-100.00 to 100.00 *1 0.01 % Y* Y 0.00 9-35
F20 DC Braking 1
(Braking starting frequency)
0.0 to 60.0 0.1 Hz Y Y 0.0 9-37
F21 (Braking level) 0 to 100 *3 1 % Y Y 0
F22 (Braking time) 0.00 (Disable), 0.01 to 30.00 0.01 s Y Y 0.00
F23 Starting Frequency 1 0.1 to 60.0 0.1 Hz Y Y 1.0 9-39
F24 (Holding time) 0.00 to 10.00 0.01 s Y Y 0.00
F25 Stop Frequency 0.1 to 60.0 0.1 Hz Y Y 0.2
F26 Motor Sound
(Carrier frequency)
0.75 to 16 1 kHz Y Y ACU:2
E:15
9-40
F27 (Tone) 0: Level 0 (Inactive) Y Y 0
1: Level 1
2: Level 2
3: Level 3
F30 Analog Output [FMA]
(Voltage adjustment)
0 to 300 1 % Y* Y 100 9-41
F31 (Function) Select a function to be monitored from the
followings.
– – Y Y 0
0: Output frequency 1 (before slip
compensation)
1: Output frequency 2 (after slip
compensation)
2: Output current *3
3: Output voltage
6: Input power
7: PID feedback amount (PV)
9: DC link bus voltage
14: Calibration
15: PID command (SV)
16: PID output (MV)
F37 0: Variable torque load N Y 1 9-42
1: Constant torque load
2: Auto-torque boost
3: Auto-energy saving operation (Variable
torque load during ACC/DEC)
4: Auto-energy saving operation (Constant
torque load during ACC/DEC)
Load Selection/
Auto Torque Boost/
Auto Energy Saving
Operation 1
5: Auto-energy saving operation (Auto-torque
boost during ACC/DEC)
F39 Stop Frequency 0.00 to 10.00 0.01 s Y Y 0.00
(Holding Time)
F42 Control Mode Selection 1 0: V/f control with slip compensation inactive N Y 0
1: Dynamic torque vector control
2: V/f control with slip compensation active
11: V/f control for PMSM drive *2
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor
can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 Available in the ROM version 0500 or later.
*3 For the single-phase 100 V class series, set the ratio relative to the reference current. Refer to Table B on page 9-19 for the
reference current.