3-26
Table 3.15 Running Status 3 (
6_24
) Bit Assignment
Bit Notation Content Bit Notation Content
15 - (Not used.) 7 - (Not used.)
14 ID2 Current detected 2 6 - (Not used.)
13 IDL Low current detected 5 OL Motor overload early warning
12 ID Current detected 4 IPF
Auto-restarting after momentary
power failure
11 OLP Overload prevention control 3 SWM2 Motor 2 selected
10 LIFE Lifetime alarm 2 - (Not used.)
9 OH
Heat sink overheat early
warning
1 FDT Frequency detected
8 TRY Auto-resetting 0 FAR Frequency arrival signal