RB unit address (Set P)
z
Each RB unit in same refrigerant system should be set an exclusive RB unit address.
00 00 00 01 00 020 1 2 00 13 14 1500 000 1 0
00 00 00 01
000
2 3
100
3
200
3
RB unit
address
Rotary SW setting
RB AD x10 RB AD x1
03
0 3
11
1 1
30
3 0
47
4 7
*Setting range 00 - 63(Arbitrary numbers can be set)
*Do not set RB unit address to the range of 64 from 99.
*Do not set the same address number to two or more RB units.
- (07-14) -
FUNCTION
SETTING
FUNCTION
SETTING