Touch panel controller setting (Set G)
z
00 01 02 03
Touch panel controller (Max. 16) *2
*1 : Set Touch panel controller address rst, to conduct the initial setting of it.
Refer to the "setting manual" for details.
*2 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote
controller and Network convertor for LONWORKS® is a maximum of 16.
z
Network convertor setting (Set H)
00
51
Group remote controller (Max. 4)*3
Single split AC
Network
convertor for Group
remote controller
(Max.16) *2
Network
convertor for
Single split AC
(Max.100) *4
*1 : Set the Rotary SW 110 and SW 111 on network convertor PCB.
*2 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote
controller and Network convertor for LONWORKS® is a maximum of 16.
*3 : Up to 64 Group remote controllers are able to connect with one VRF Network system.
*4 : When connecting the Network convertor for Single split AC , set up the number so that the Refrigerant circuit
address number of outdoor unit and indoor unit does not overlap .
And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refriger-
ant circuit address of the outdoor unit and the indoor unit is a maximum of 100.
- (07-15) -