Group remote controller setting (Set I)
z
Group remote controller (Max. 4) *3
Network
convertor for
Group remote
controller
(Max.16) *2
*1 : Set group remote controller address rst, to conduct the initial setting of it.
*2 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote
controller and Network convertor for LONWORKS® is a maximum of 16.
*3 : Up to 64 Group remote controllers are able to connect with one VRF Network system.
z
Dual remote control switch (Set J)
When 2 wired remote controllers are connected to the remote control group, turn the SW 2 of
DIP Switch 1 of Slave Remote Controller ON.
Slave remote controller will not be valid for timer setting.
●
Last command is priority.
●
SW2 OFF ON
of DIP Switch 1
SW2 OFF
of DIP Switch 1
Remote controller unit PCB When only 1 remote controller will connect,
Setting by SW 2 of DIP Switch 1 this SW 2 of DIP Switch 1 must be set OFF.
Signal amplier address (Set K)
z
1
2
3
Signal amplier
- (07-16) -
FUNCTION
SETTING
FUNCTION
SETTING