197
Parameters of Transducer Block
Function Block Parameters
100 2100 SIGN_DATA_
SAVE
1 Saves the measurements of the standard
actuator signature to non-volatile memory as
record data. 1 = off
101 2101 SIGN_
UPLOAD
_DATABASE
1 Parameter used to specify the measured data
to be uploaded. Set this parameter, and the
related parameters will be read.
102 2102 SIGN_
UPLOAD
_POINTER
0 Pointer that indicates the leading position of
the data to be uploaded from SIGN_DATA_X or
SIGN_DATA_Y, and used when there are 20 or
more data values measured.
103 2103 SIGN_DATA_
X
0 Parameter used to upload the measured
signature data (input data).
104 2104 SIGN_DATA_
Y
0 Parameter used to upload the measured
signature data (output data).
105 2105 SIGN_MEAS_
DATE
01/01/00
00:00:00.000
Parameter used to upload the date and time of
signature measurement
106 2106 SIGN_
HEADER
_DATA
+inf Parameter used to upload the ambient
temperature and settings at signature
measurement
107 2107 STD_ACT_
SIGN
_SET
180, 180, 50 Settings of the standard actuator signature
108 2108 EXT_ACT_
SIGN
_SET
0, 100, 180,
180, 50, 200
Settings of the extended actuator signature
and high resolution actuator signature
109 2109 STEP_RESP
_SET
45, 55, 100,
600
Settings of step levels for step response test
110 2110 POSITIONER
_SIGN_SET
0, 100, 10, 30,
30
Settings of the positioner signature
111 2111 SERVO_
WARN
_HI_LIM
80 % of MV High-limit alarm setting for Servo Output Drift
warning
112 2112 SERVO_
WARN_
LO_LIM
20 % of MV Low-limit alarm setting for Servo Output Drift
warning
Table 61 Transducer Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description