FVP 110 Fieldbus Valve Positioner Manual
196
GE Energy
90 2090 RELEASE
_FAILSAFE
As specified
upon ordering
O/S Used to release the block from the fail-safe
state.
When the value of this parameter is 3, writing 1
will release the block from the fail-safe state.
1 = clear, non-latch (normal state)
2 = active, latched (during fail-safe state)
3 = clear, latched (cause has been cleared but
failsafe action is still on).
91 2091 MODEL As specified
upon ordering
— Model code
92 2092 DEV_
OPTIONS
0x000D (or
0X0001 if PID
option is
specified)
— Indicates whether any software options are
provided.
93 2093 PRESS_
SENS
_INSTALLED
1 — Indicates whether a pressure sensor is
equipped:
1 = equipped
2 = not equipped
94 2094 ACTUATOR_
TYPE
As specified
upon ordering
— Actuator type
1 = single acting
2 = double acting
95 2095 RELAY_TYPE 1 Control relay type:
1 = direct acting
96 2096 SIGN_MEAS_
EXEC
1 O/S Carries outs signature measurement. 1 = off
97 2097 SIGN_MEAS
_RESULT
1 — Indicates the signature measurement status
and result.
1 = succeeded
98 2098 SIGN_MEAS_
STATE
0 — Indicates the progress of signature
measurement.
99 2099 SIGN_MEAS
_COUNTER
0 — Indicates the number of measured data sets.
The count is reset to zero when the power is
turned off or measurement of a new signature
is performed.
Table 61 Transducer Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description