195
Parameters of Transducer Block
Function Block Parameters
81 2081 TOTAL_
CLOSE
_TIME
0 hour Total time where valve position is equal to or
less than OPEN_CLOSE_THRESHOLD. To
reset the count, write 0.
82 2082 OPEN_
CLOSE
_
THRESHOLD
0.25% Threshold value for TOTAL_OPEN_TIME and
TOTAL_CLOSE_TIME.
83 2083 OPEN_TIME_
LIM
2^32-1 hours High-limit alarm setting for
TOTAL_OPEN_TIME.
When TOTAL_OPEN_TIME has reached this
setting, a block alarm is generated.
84 2084 CLOSE_TIME
_LIM
2^32-1 hours High-limit alarm setting for
TOTAL_CLOSE_TIME.
When TOTAL_CLOSE_TIME has reached this
setting, a block alarm is generated.
85 2085 TOTAL_
NEAR
_CLOSE_TIM
0 O/S Total time period when the valve position is
equal to or less than the value set in
NEAR_CLOSE_THRESHOLD (judged as
when the valve is nearly closed). To reset the
count, write 0.
86 2086 NEAR_
CLOSE
_
THRESHOLD
3.0 % Threshold for judging that the valve is nearly
closed
87 2087 NEAR_
CLOSE
_TIME_LIM
2^32-1 hours High-limit alarm setting for
TOTAL_NEAR_CLOSE_TIM. When
TOTAL_NEAR_CLOSE_TIM has reached this
setting, a block alarm is generated.
88 2088 DEVIATION_
LIM
110% Deviation high limit (%)
89 2089 DEVIATION_
TIME
_TH
10, -1 (off) If the time period when the deviation is
continuously equal to or greater than
DEVIATION_LIM has reached the time set for
the first value in this parameter, a block alarm
is generated. If it has reached the time set for
the second value, the instrument transfers to
fault state. Negative value means off.
Table 61 Transducer Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description