FVP 110 Fieldbus Valve Positioner Manual
194
GE Energy
67 2067 AUTO_TUNE
_RESULT
1 — Indicates the result of auto tuning.
68 2068 AUTO_TUNE
_STATE
0 — Indicates auto tuning sequence number.
69 2069 SERVO_RET
_TO
_DFLT
1 O/S Writing 2 to this parameter resets all control
parameters to the defaults:
1 = off
2 = set (to the defaults)
70 2070 ADVAL_FW – — Digital value of valve control signal, setpoint
equivalent to A/D value of valve position signal.
71 2071 ADVAL_BW – — A/D value of valve position signal
72 2072 ADVAL_
PRESS
– — A/D value of pressure from sensor
73 2073 ADVAL_T – — A/D value of temperature from sensor
74 2074 TOTAL_
CYCLE
_COUNT
0 O/S Total number of cycles. To reset the count,
write 0.
75 2075 CYCLE
_DEADBAND
0.25% — Dead band of cycle counting
76 2076 CYCLE_
COUNT
_LIM
2^32-1 High-limit alarm setting for
TOTAL_CYCLE_COUNT.
When TOTAL_CYCLE_COUNT has reached
this setting, a block alarm is generated.
77 2077 TOTAL_
TRAVEL
0 O/S Total amount of travel. To reset the count, write
0.
78 2078 TRAVEL
_DEADBAND
0.25% Dead band of travel integration
79 2079 TRAVEL_
LIM
2^32-1 High-limit alarm setting for TOTAL_TRAVEL.
When TOTAL_TRAVEL has reached this
setting, a block alarm is generated.
80 2080 TOTAL_
OPEN
_TIME
0 hour Total time other than counted for
TOTAL_CLOSE_TIME. To reset the count,
write 0.