FVP 110 Fieldbus Valve Positioner Manual
200
GE Energy
18 5018 SP_RATE_
DN
+INF Rate-of-decrease limit for SP effective in
AUTO, CAS, and RCAS modes. If this
parameter is 0, no limit is applied to the rate of
decrease.
19 5019 SP_RATE_
UP
+INF Rate-of-increase limit for SP effective in AUTO,
CAS, and RCAS modes. If this parameter is 0,
no limit is applied to the rate of increase.
20 5020 SP_HI_LIM 100 Upper limit for setpoint (SP)
21 5021 SP_LO_LIM 0 Lower limit for setpoint (SP)
22 5022 CHANNEL 1 O/S
Defines the channel number of the
hardware channel connected to the
transducer block. Always set to 1 for the
AO block in a FVP110.
23 5023 FSTATE_
TIME
0 second
Defines the time from when the fault state
of the RCAS_IN or CAS_IN is detected to
when the output should be set to the level
preset in FSTATE_VAL (this action takes
place only if Fault State to value is set as
true in I/O_OPTS).
24 5024 FSTATE_VAL 0
Preset output level for fault state. See
above.
25 5025 BKCAL_OUT – —
Value to be input to BKCAL_IN of the
downstream block; used by the
downstream block to prevent reset windup
and perform bumpless transfer to
closed-loop control.
26 5026 RCAS_IN –
Remote cascade setpoint set by the host
computer, etc.
27 5027 SHED_OPT 1
Defines the mode shedding action to be
taken upon occurrence of time-out of
communication in a mode using the
remote setpoint.
28 5028 RCAS_OUT – —
Remote setpoint sent to a host computer,
etc.
Table 62 AO Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description