FVP 110 Fieldbus Valve Positioner Manual
206
GE Energy
7 8007 PV — — Indicates the primary analog value (or the
corresponding process value) used to execute
the specified actions, and the status of that
value.
8 8008 SP — Auto Setpoint of the block.
9 8009 OUT — Man Value and status of output.
10 8010 PV_SCALE 0-100% O/S Upper and lower scale limit values used for
scaling of the input (IN) value.
11 8011 OUT_SCALE 0-100% O/S Upper and lower scale limit values used for
scaling of the control output (OUT) value to the
values in the engineering unit.
12 8012 GRANT_DEN
Y
0 Option to control access from the host
computer and local control panel to tuning and
alarm parameters.
13 8013 CONTROL_O
PTS
0x0000 O/S Defines block actions depending on block
status conditions.
14 8014 STATUS_OP
TS
0x0000 O/S Defines options for control actions of block.
15 8015 IN 0 Controlled-value input.
16 8016 PV_FTIME 0 Time constant (in seconds) of the first-order lag
filter applied to IN
17 8017 BYPASS 1 Man Determines whether to bypass control
computation.
1 = off; do not bypass.
2 = on; bypass.
18 8018 CAS_IN 0 Cascade setpoint.
19 8019 SP_RATE_D
N
+INF Rate-of-decrease limit for setpoint (SP)
20 8020 SP_RATE_U
P
+INF Rate-of-increase limit for setpoint (SP)
21 8021 SP_HI_LIM 100 Upper limit for setpoint (SP)
22 8022 SP_LO_LIM 0 Lower limit for setpoint (SP)
23 8023 GAIN 1
Proportional gain (= 100 / proportional
band).
Table 65 PID Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description